YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
517
6.10
Bypass Status Messages
The bypass HOA keypad will show these status messages on line 1 of the keypad display during the conditions listed
below. These are not faults or alarms.
Keypad Display
Description
Powering Up
Shown on initial power up of the bypass system. This message goes away when the power up initialization is complete and
communication is established to the drive, or when the bypass determines that the drive is not connected or energized.
Idle
The bypass is in an Idle state with no active Run command. There are no active faults or alarms.
Drive Not Ready
The drive is not in a ready state. The drive will not run if a Run command is asserted. You can run the system in Bypass
Mode.
Safety Open
A safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Fire Stat Open
A Fire Stat safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Freeze Stat Open
A Freeze Stat safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Smoke Alarm active
A Smoke Alarm safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Over Pressure Detected
An Over Pressure safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Low Suction Detected
A Low Suction safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Vibration Detected
A Vibration safety programmed to a bypass digital input is not closed and there is no active Run command.
This message will change to an alarm when there is an active Run command.
Interlock Open
Programmed BAS Interlock is not closed. The unit will not run when it receives a Run command.
Drive Pre Running
The drive received a Run command and the drive is entering the programmed pre-run. When the pre-run conditions are
finished, the drive will enter drive run.
Drive Run Commanded
The bypass has commanded the drive to run, but it has not yet detected t that the drive is running.
Restart Delay Active
There is an active Run Command, but the programmed restart delay is active and the drive cannot run. The keypad shows this
display on power-up or when there is a brief power loss to the bypass unit.
Drive Running
The unit is running in Drive Mode.
Drive Stopping
The Run command to the drive was removed, and the drive is ramping to stop.
Running in Bypass
The unit is running in Bypass Mode.
Entering Energy Savings
Energy savings conditions have been detected. This functionality is programmed using parameters Z1-16 through Z1-23.
When entering energy savings, the unit is running at the energy savings bump frequency and when it is finished, it will
switch into the bypass run state.
Energy Savings Active
Energy Savings Mode is active and the unit is running in Bypass Mode.
Exiting Energy Savings
Energy Savings conditions are no longer present and the unit is leaving Energy Savings and returning to Drive Mode. The
exit conditions are when the frequency reference changes from the programmed Energy Savings frequency reference in
Z1-
17
.
Auto Transfer Active
Auto transfer was enabled in
Z1-05
and the unit detected a drive fault during an active drive run. The unit will run in Bypass
Mode.
Remote Transfer Active
A Remote Transfer was asserted and the unit is currently running in Bypass Mode.
Emergency Override Drive FWD
An Emergency Override Drive FWD was asserted by a bypass digital input or through serial or option board communications
to the bypass board.
Emergency Override Drive REV
An Emergency Override Drive REV was asserted by a bypass digital input or through serial or option board communications
to the bypass board.
Emergency Override Bypass
An Emergency Override Bypass was asserted by a bypass digital input or through serial or option board communications to
the bypass board. This message also appears when Emergency Override Drive was active, there was a drive fault, and
Z1-10
= 1 [Transfer to Bypass]
.
Faulted
The unit is in Drive Mode it detected a drive fault or bypass fault, or the unit is in Bypass Mode and it detected a bypass-
specific fault.
Soft Start On Delay
There is a Run command and the unit is waiting for the programmed on delay time in
Z1-43
before asserting the soft starter
run.
Soft Starter Ramping down
Parameter
Z1-42 = 2 [Ramp to Stop]
and the Run command was removed. The soft starter will ramp to stop.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...