YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
609
9.8
E: Motor Parameters
◆
E1: V/f Pattern for Motor 1
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
E1-01
(0300)
Input AC Supply Voltage
Sets the drive input voltage.
208/240 V: 240 V,
480 V: 480 V
(208/240 V: 155 - 255 V,
480 V: 310 - 510 V)
E1-03
(0302)
V/f Pattern Selection
Sets the V/f pattern for the drive and motor. You can use one of the preset patterns or you
can make a custom pattern.
0 : Const Trq, 50Hz base, 50Hz max
1 : Const Trq, 60Hz base, 60Hz max
2 : Const Trq, 50Hz base, 60Hz max
3 : Const Trq, 60Hz base, 72Hz max
4 : VT, 50Hz, 65% Vmid reduction
5 : VT, 50Hz, 50% Vmid reduction
6 : VT, 60 Hz, 65% Vmid reduction
7 : VT, 60Hz, 50% Vmid reduction
8 : High Trq, 50Hz, 25% Vmin boost
9 : High Trq, 50Hz, 65% Vmin boost
A : High Trq, 60Hz, 25% Vmin boost
B : High Trq, 60Hz, 65% Vmin boost
C : High Freq, 60Hz base, 90Hz max
D : High Freq, 60Hz base, 120Hz max
E : High Freq, 60Hz base, 180Hz max
F : Custom
Note:
•
Set the correct V/f pattern for the application and operation area. An incorrect V/f
pattern can decrease motor torque and increase current from overexcitation.
•
Parameter
A1-03 [Initialize Parameters]
will not initialize the value of
E1-03
.
F
(0 - F)
E1-04
(0303)
Maximum Output
Frequency
Sets the maximum output frequency for the V/f pattern.
60.0 Hz
(40.0 to 400.0 Hz)
E1-05
(0304)
Maximum Output Voltage Sets the maximum output voltage for the V/f pattern.
208/240 V: 230.0 V,
480 V: 460.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
E1-06
(0305)
Base Frequency
Sets the base frequency for the V/f pattern.
60.0 Hz
(0.0 - E1-04)
E1-07
(0306)
Mid Point A Frequency
Sets a middle output frequency for the V/f pattern.
30.0 Hz
(0.0 - E1-04)
E1-08
(0307)
Mid Point A Voltage
Sets a middle output voltage for the V/f pattern.
Determined by o2-04
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
E1-09
(0308)
Minimum Output
Frequency
Sets the minimum output frequency for the V/f pattern.
1.5 Hz
(Determined by E1-04)
E1-10
(0309)
Minimum Output Voltage Sets the minimum output voltage for the V/f pattern.
10.2 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
E1-11
(030A)
Expert
Mid Point B Frequency
Sets a middle output frequency for the V/f pattern.
0.0 Hz
(0.0 - E1-04)
E1-12
(030B)
Expert
Mid Point B Voltage
Sets a middle point voltage for the V/f pattern.
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
E1-13
(030C)
Expert
Base Voltage
Sets the base voltage for the V/f pattern.
0.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...