YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
619
Setting Value
Function
Description
Ref.
AD
Select PI2 Control PI
Parameters
Sets the command to use the
S3-06 [PI2 Control Proportional Gain]
and
S3-07 [PI2 Control Integral Time]
values
instead of the
b5-02 [Proportional Gain (P)]
and
b5-03 [Integral Time (I)]
values. Set
S3-01 = 0 [PI2 Control Enable
Selection = Disabled]
to enable this function.
Note:
This multi-function input does not have an effect on PI2 Control. Use this input for the primary PI controller (
b5-
xx
).
B9
Disable Pre-charge
Sets the command to disable the Pre-charge function.
ON : Pre-charge function is disabled
188
!Thermostat Fault
Sets the drive to show the
VLTS [Thermostat Fault]
when the input terminal is OFF.
Note:
This function is active when the drive is running.
1A8
!PI2 Control Disable
Sets the command to disable the PI2 Control function. Parameter
S3-12 [PI2 Control Disable Mode Sel]
sets the
output performance.
ON : Disabled
OFF : Enabled
◆
H2: Digital Outputs
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
H2-01
(040B)
Term M1-M2 Function
Selection
Sets the function for MFDO terminal M1-M2.
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in
through mode.
0
(0 - 1FF)
H2-02
(040C)
Term M3-M4 Function
Selection
Sets the function for MFDO terminal M3-M4.
Note:
Set this parameter to
F
when the terminal is not being used or to use the terminal in
through mode.
1
(0 - 1FF)
H2-03
(040D)
Term M5-M6 Function
Selection
Sets the function for MFDO terminal M5-M6.
Note:
When you do not use this terminal, or when you will use the terminal in through mode,
set this parameter to
F
.
2
(0 - 1FF)
H2-06
(0437)
Watt Hour Output Unit
Selection
Sets the unit for the output signal when
H2-01 to H2-03 = 39 [MFDO Function Selection
= Watt Hour Pulse Output]
.
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
0
(0 - 4)
H2-07
(0B3A)
Modbus Register 1
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
H2-09
(0B3C)
Modbus Register 2
Address Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
H2-40
(0B58)
Mbus Reg 15E0h bit0
Output Func
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
H2-41
(0B59)
Mbus Reg 15E0h bit1
Output Func
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
H2-42
(0B5A)
Mbus Reg 15E0h bit2
Output Func
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
F
(0 - 1FF)
H2-60
(1B46)
Expert
Term M1-M2 Secondary
Function
Sets the second function for terminal M1-M2. Outputs the logical calculation results of the
terminals assigned to functions by
H2-01 [Term M1-M2 Function Selection]
.
F
(0 - FF)
H2-61
(1B47)
Expert
Terminal M1-M2 Logical
Operation
Sets the logical operation for the functions set in
H2-01 [Term M1-M2 Function Selection]
and
H2-60 [Term M1-M2 Secondary Function]
.
0
(0 - 8)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...