622
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Setting Value
Function
Description
Ref.
1B
During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops switching
and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
1E
Executing Auto-Restart
The terminal activates when the Auto Restart function is trying to restart after a fault.
1F
Motor Overload Alarm
(oL1)
The terminal activates when the electronic thermal protection value of the motor overload protective function is a
minimum of 90% of the detection level.
20
Drive Overheat Pre-
Alarm (oH)
The terminal activates when the drive heatsink temperature is at the level set with
L8-02 [Overheat Alarm Level]
.
21
Safe Torque OFF
The terminal activates (safety stop state) when the safety circuit and safety diagnosis circuit are operating correctly and
when terminals H1-HC and H2-HC are OFF (Open).
ON : Safety stop state
OFF : Safety circuit fault or RUN/READY
2F
Maintenance Notification
The terminal activates when drive components are at their estimated maintenance period.
Tells the user about the maintenance period for these items:
•
IGBT
•
Cooling fan
•
Capacitor
•
Soft charge bypass relay
37
During Frequency Output The terminal activates when the drive outputs frequency.
ON : The drive outputs frequency.
OFF : The drive does not output frequency.
38
Drive Enabled
This terminal activates when the
H1-xx = 6A [Drive Enable]
terminal activates.
39
Watt Hour Pulse Output
Outputs the pulse that shows the watt hours.
3A
Drive Overheat Alarm
The terminal activates when the drive heatsink temperature is at the
L8-02 [Overheat Alarm Level]
setting while
L8-03
= 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and the drive is running.
3D
During Speed Search
The terminal activates when the drive is doing speed search.
42
Pressure Reached
The terminal activates when the drive is at the Pressure Setpoint.
4C
During Fast Stop
The terminal activates when the fast stop is in operation.
4D
oH Pre-Alarm Reduction
Limit
The terminal activates when
L8-03 = 4 [Overheat Pre-Alarm Selection = Operate at Reduced Speed (L8-19)]
and
oH
[Heatsink Overheat]
does not clear after the drive decreases the frequency for 10 cycles.
51
Sequence Timer 1
The terminal activates when Sequence Timer 1 is active.
52
Sequence Timer 2
The terminal activates when Sequence Timer 2 is active.
53
Sequence Timer 3
The terminal activates when Sequence Timer 3 is active.
54
Sequence Timer 4
The terminal activates when Sequence Timer 4 is active.
58
UL6 Underload Detected
The terminal activates when the drive detected
UL6 [Underload or Belt Break Detected]
.
60
Internal Cooling Fan
Failure
The terminal activates when the drive detects a cooling fan failure in the drive.
62
Modbus Reg 1 Status
Satisfied
The terminal activates when the bit specified by
H2-08 [Modbus Register 1 Bit Select]
for the MEMOBUS register
address set with
H2-07 [Modbus Register 1 Address Select]
activates.
63
Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by
H2-10 [Modbus Register 2 Bit Select]
for the MEMOBUS register
address set with
H2-09 [Modbus Register 2 Address Select]
activates.
69
External Power 24V
Supply
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : An external 24V power supply supplies power.
OFF : An external 24V power supply does not supply power.
6A
Data Logger Error
The terminal activates when the drive detects
LoG [Com Error / Abnormal SD card]
.
71
Low PI2 Control
Feedback Level
The terminal activates when the PI2 Control Feedback Level is less than
S3-13 [PI2 Control Low Feedback Lvl]
.
72
High PI2 Control
Feedback Level
The terminal activates when the PI2 Control Feedback Level is more than
S3-15 [PI2 Control High Feedback Lvl]
.
89
Output Current Lim
The terminal activates when the output current limit is limiting the drive output speed.
94
Loss of Prime
The terminal activates when the drive is in an
LOP [Loss of Prime]
condition.
95
Thermostat Fault
The terminal activates when the terminal set for
H1-xx = 88 [MFDI Function Selection = Thermostat Fault]
is active.
96
High Feedback
The terminal activates when the drive is in a High Feedback Condition as specified by
Y1-11 [High Feedback Level]
and
Y1-12 [High Feedback Lvl Fault Dly Time]
and when the drive detects an
HFB [High Feedback Sensed]
fault or
an
HIFB [High Feedback Sensed]
alarm.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...