YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
MFAO Signal Level
U2-05
(0084)
Output Current@Fault
Shows the output current at the fault that occurred most recently.
Use
U1-03 [Output Current]
to monitor the output current. The keypad shows the value of
U1-03
in
amperes (A).
When you use serial communications to show the monitor, the current is
“
8192 = drive rated current
(A)
”
. Use the formula:
“
Numerals being displayed / 8192 × drive rated current (A)
”
to use the serial
communication current value shown in the monitor.
Unit: Determined by the drive model.
•
0.01 A: 2011 to 2046, 4005 to 4014
•
0.1 A: 2059 to 2273, 4021 to 4302
No signal output available
U2-07
(0086)
Output Voltage@Fault
Shows the output voltage reference at the fault that occurred most recently.
Use
U1-06 [Output Voltage Ref]
to monitor the output voltage reference.
Unit: 0.1 V
No signal output available
U2-08
(0087)
DC Bus Voltage@Fault
Shows the DC bus voltage at the fault that occurred most recently.
Use
U1-07 [DC Bus Voltage]
to monitor the DC bus voltage.
Unit: 1 V
No signal output available
U2-09
(0088)
Output Power @ Fault
Shows the output power at the fault that occurred most recently.
Use
U1-08 [Output Power]
to monitor the output power.
Unit: 0.1 kW
No signal output available
U2-11
(008A)
Byp Inp Terminal Status @
Fault
Shows the status of the bypass digital input terminals at the most recent fault where 1 = (ON) and 0 =
(OFF).
For example,
U2-11
shows
“
00000011
”
when terminals S1 and S2 are ON.
Use
Ub-02 [Bypass Digital Input Status]
to monitor the terminal status.
bit 0 : Terminal S1
bit 1 : Terminal S2
bit 2 : Terminal S3
bit 3 : Terminal S4
bit 4 : Terminal S5
bit 5 : Terminal S6
bit 6 : Terminal S7
bit 7 : Not used (normal value of 0).
No signal output available
U2-12
(008B)
Byp Relay Status @ Fault
Shows the status of the bypass digital output terminals at the most recent fault where 1 = (ON) and 0
= (OFF).
For example,
U2-12
shows
“
00000011
”
when terminals M1 and M3 are ON.
Use
Ub-02 [Bypass Digital Output Status]
to monitor the terminal status.
bit 0 : Terminals M1-M2
bit 1 : Terminals M3-M4
bit 2 : Terminals M5-M6
bit 3 : Not used (normal value of 0).
bit 4 : Not used (normal value of 0).
bit 5 : Not used (normal value of 0).
bit 6 : Not used (normal value of 0).
bit 7 : Fault relay MA/MB-MC
No signal output available
U2-13
(008C)
Bypass Status @ Fault
Shows the status of the bypass at the most recent fault where 1 = (ON) and 0 = (OFF).
For example,
U2-13
shows
“
00000001
”
during run.
Use
Ub-05 [Bypass Status 1]
to monitor the bypass.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive ready
bit6 : During minor fault detection
bit7 : During fault detection
No signal output available
U2-14
(008D)
Elapsed Time @ Fault
Shows the cumulative operation time of the drive at the fault that occurred most recently.
Use
U4-01 [Cumulative Ope Time]
to monitor the cumulative operation time.
Unit: 1 h
No signal output available
U2-15
(07E0)
SFS Output @ Fault
Shows the output frequency after soft start at the fault that occurred most recently.
Use
U1-16 [SFS Output Frequency]
to monitor the output frequency after soft start.
Unit: 0.01 Hz
No signal output available
U2-16
(07E1)
q-Axis Current@Fault
Shows the q-Axis current of the motor at the fault that occurred most recently.
Use
U6-01 [Iq Secondary Current]
to monitor the q-Axis current of the motor.
Unit: 0.1 %
No signal output available
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...