YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
675
No.
(Hex.)
Name
Description
MFAO Signal Level
U2-20
(008E)
Heatsink Temp @Fault
Shows the heatsink temperature at the fault that occurred most recently.
Use
U4-08 [Heatsink Temperature]
to monitor the temperature of the heatsink.
Unit: 1 °C
No signal output available
U2-30
(3008)
Fault 1 YYYY
Shows the year when the most recent fault occurred.
No signal output available
U2-31
(3009)
Fault 1 MMDD
Shows the month and day when the most recent fault occurred.
No signal output available
U2-32
(300A)
Fault 1 HHMM
Shows the time when the most recent fault occurred.
No signal output available
◆
U3: Fault History
No.
(Hex.)
Name
Description
MFAO Signal Level
U3-01
(0090)
1st MostRecent Fault
Shows the fault history of the most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-02
(0091)
2nd MostRecent Fault
Shows the fault history of the second most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-03
(0092)
3rd MostRecent Fault
Shows the fault history of the third most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-04
(0093)
4th MostRecent Fault
Shows the fault history of the fourth most recent fault.
Note:
The drive saves this fault history to two types of registers at the same time for the MEMOBUS/
Modbus communications.
No signal output available
U3-05
(0804)
5th MostRecent Fault
Shows the fault history of the fifth most recent fault.
No signal output available
U3-06
(0805)
6th MostRecent Fault
Shows the fault history of the sixth most recent fault.
No signal output available
U3-07
(0806)
7th MostRecent Fault
Shows the fault history of the seventh most recent fault.
No signal output available
U3-08
(0807)
8th MostRecent Fault
Shows the fault history of the eighth most recent fault.
No signal output available
U3-09
(0808)
9th MostRecent Fault
Shows the fault history of the ninth most recent fault.
No signal output available
U3-10
(0809)
10th MostRecentFault
Shows the fault history of the tenth most recent fault.
No signal output available
U3-11
(0094)
ElapsedTime@1stFault
Shows the cumulative operation time when the most recent fault occurred.
Note:
The drive saves this cumulative operation time to two types of registers at the same time for the
MEMOBUS/Modbus communications.
Unit: 1 h
No signal output available
U3-12
(0095)
ElapsedTime@2ndFault
Shows the cumulative operation time when the second most recent fault occurred.
Note:
The drive saves this cumulative operation time to two types of registers at the same time for the
MEMOBUS/Modbus communications.
Unit: 1 h
No signal output available
U3-13
(0096)
ElapsedTime@3rdFault
Shows the cumulative operation time when the third most recent fault occurred.
Note:
The drive saves this cumulative operation time to two types of registers at the same time for the
MEMOBUS/Modbus communications.
Unit: 1 h
No signal output available
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...