10.6 MEMOBUS/Modbus Communications
762
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Register No.
(Hex.)
Description
00C9
Minor Fault Description 3
bit 0
dEv [Speed Deviation]
bit 1
Reserved
bit 2
oPr [Keypad Connection Fault]
bit 3
CE [Run at H5-34 (CE Go-To-Freq)]
bit 4
bUS [Option Communication Error]
bit 5
CALL [Serial Comm Transmission Error]
bit 6
oL1 [Motor Overload]
bit 7
oL2 [Drive Overloaded]
bit 8
Reserved
bit 9
EF0 [Option Card External Fault]
bit A
rUn [Motor Switch during Run]
bit B
Reserved
bit C
CALL [Serial Comm Transmission Error]
bit D
UL3 [Undertorque Detection 1]
bit E
UL4 [Undertorque Detection 2]
bit F
SE [Modbus Test Mode Error]
00CA
Minor Fault Description 4
bit 0
Reserved
bit 1
oH3 [Motor Overheat (PTC Input)]
bit 2 - 8
Reserved
bit 9
dnE [Drive Disabled]
bit A - F
Reserved
00CB
Minor Fault Description 5
bit 0 - 2
Reserved
bit 3
HCA [High Current Alarm]
bit 4
LT-1 [Cooling Fan Maintenance Time]
bit 5
LT-2 [Capacitor Maintenance Time]
bit 6 - 7
Reserved
bit 8
EF1 [External Fault (Terminal S1)]
bit 9
EF2 [External Fault (Terminal S2)]
bit A
SToF [Safe Torque OFF Hardware]
bit B - F
Reserved
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...