YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
291
■
89: Output Current Lim
Setting Value
Function
Description
89
Output Current Lim
The terminal activates when the output current limit is limiting the drive output speed.
■
94: Loss of Prime
Setting Value
Function
Description
94
Loss of Prime
The terminal activates when the drive is in an
LOP [Loss of Prime]
condition.
■
95: Thermostat Fault
Setting Value
Function
Description
95
Thermostat Fault
The terminal activates when the terminal set for
H1-xx = 88 [MFDI Function Selection = Thermostat Fault]
is active.
■
96: High Feedback
Setting Value
Function
Description
96
High Feedback
The terminal activates when the drive is in a High Feedback Condition as specified by
Y1-11 [High Feedback Level]
and
Y1-12
[High Feedback Lvl Fault Dly Time]
and when the drive detects an
HFB [High Feedback Sensed]
fault or an
HIFB [High Feedback
Sensed]
alarm.
■
97: Low Feedback
Setting Value
Function
Description
97
Low Feedback
The terminal activates when the drive is in a Low Feedback Condition as specified by
Y1-08 [Low Feedback Level]
and
Y1-09 [Low
Feedback Lvl Fault Dly Time]
and when the drive detects an
LFB [Low Feedback Sensed]
fault or an
LOFB [High Feedback
Sensed]
alarm.
■
9E: Low PI Auxiliary Control Level
Setting Value
Function
Description
9E
Low PI Auxiliary Control
Level
The terminal activates when the PI Aux Feedback Level is less than
YF-09 [PI Aux Control Low Level Detect]
or if the drive detects
an
LOAUX [Low PI Aux Feedback Level]
fault.
■
9F: High PI Auxiliary Control Level
Setting Value
Function
Description
9F
High PI Auxiliary Control
Level
The terminal activates when the PI Aux Feedback Level is more than
YF-12 [PI Aux Control High Level Detect]
or if the drive
detects an
HIAUX [High PI Aux Feedback Level]
fault.
■
A9: RELAY Operator Control
Setting Value
Function
Description
A9
RELAY Operator Control
The terminal changes to OFF or ON when you push the RELAY (
) button. When the terminal is ON, push
to turn
it OFF. When the terminal is OFF, push
to turn in ON.
■
AB: Thrust Mode
Setting Value
Function
Description
AB
Thrust Mode
The terminal activates when the output frequency is between 0.0 Hz and the value set in
Y4-12 [Thrust Frequency]
and the Thrust
Bearing function is active.
■
AC: Setpoint Not Maintained
Setting Value
Function
Description
AC
Setpoint Not Maintained
The terminal activates when the drive detects
NMS [Setpoint Not Met]
condition.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...