YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
317
5.8
L: Protection Functions
L parameters
set the following functions.
•
Motor Overload Protection
•
Operation During Momentary Power Loss
•
Stall Prevention
•
Speed Detection
•
Auto Restart
•
Detection of Overtorque/Undertorque
•
Torque Limit
•
Hardware Protection
◆
L1: Motor Protection
L1 parameters
set the motor overload protection function.
■
L1-01: Motor Overload (oL1) Protection
No.
(Hex.)
Name
Description
Default
(Range)
L1-01
(0480)
Motor Overload (oL1)
Protection
Sets the motor overload protection with electronic thermal protectors.
1
(0, 1)
This parameter enables and disables the motor overload protection with electronic thermal protectors.
The cooling capability of the motor changes when the speed control range of the motor changes. Use an electronic
thermal protector that aligns with the permitted load characteristics of the motor to select motor protection.
The electronic thermal protector of the drive uses these items to calculate motor overload tolerance and supply
overload protection for the motor:
•
Output Current
•
Output Frequency
•
Motor thermal characteristics
•
Time characteristics
If the drive or bypass board detects motor overload, the drive will trigger an
oL1[Motor Overload]
or the bypass
board will trigger an
FB05 [Motor Overload]
and stop output.
Set
H2-01 = 1F [Term M1-M2 Function Selection = Motor Overload Alarm (oL1)]
to set a motor overload alarm. If
the motor overload level is more than 90% of the
oL1
detection level, the output terminal turns ON and triggers an
overload alarm.
0 : Disabled
Disable motor protection when motor overload protection is not necessary or when the drive is operating more than
one motor.
Refer to
for an example of the circuit configuration to connect more than one motor to one drive.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...