5.10 o: Keypad-Related Settings
356
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
•
Select the units for these parameters:
–
d1-01 [Reference 1]
to
d1-08 [Reference 8]
,
d1-17 [Jog Reference]
–
U1-01 [Frequency Reference]
–
U1-02 [Output Frequency]
–
U1-05 [Motor Speed]
–
U1-16 [SFS Output Frequency]
–
U4-14 [PeakHold Output Freq]
–
U5-07 [AUTO Mode Freq Ref]
–
U5-08 [HAND Mode Freq Ref]
0 : 0.01Hz units
1 : 0.01% units
The maximum output frequency is 100%.
2 : min
-1
(r/min) unit
The drive uses the maximum output frequency and number of motor poles calculate this value automatically.
Note:
When you set
o1-03 = 2 [r/min]
, make sure that you set the number of motor poles in
E2-04 [Motor Pole Count]
.
3 : User Units (o1-09 -o1-11)
Uses
o1-09 [Freq. Reference Display Units]
,
o1-10 [User Units Maximum Value]
, and
o1-11 [User Units Decimal
Position]
to set the unit of measure. The value of parameter
o1-10
is the value when you remove the decimal point
from the maximum output frequency. Parameter
o1-11
is to the number of digits after the decimal point in the
maximum output frequency.
To display a maximum output frequency of 100.00, set parameters to these values:
•
o1-10 = 10000
•
o1-11 = 2 [User Units Decimal Position = 2 Dec (XXX.XX)]
■
o1-05: LCD Contrast Adjustment
No.
(Hex.)
Name
Description
Default
(Range)
o1-05
(0504)
RUN
LCD Contrast Adjustment
Sets the contrast of the LCD display on the keypad.
5
(0 - 10)
When you decrease the setting value, the contrast of the LCD display decreases. When you increase the setting value,
the contrast increases.
■
o1-09: Freq. Reference Display Units
No.
(Hex.)
Name
Description
Default
(Range)
o1-09
(051C)
Freq. Reference Display
Units
Sets the unit of display for the frequency reference parameters and frequency-related monitors when
o1-03 = 3 [Frequency Display Unit Selection = User Units (o1-09 ~ o1-11)]
.
50
(0 - 50)
0 : “WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 :
°
F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...