SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
407
5.13
Y: Application Features
◆
Y1: Application Basics
■
Y1-04: Sleep Wake-up Level
No.
(Hex.)
Name
Description
Default
(Range)
Y1-04
(3C03)
RUN
Sleep Wake-up Level
Sets the level that feedback must be less than for the time set in
Y1-05 [Sleep Wake-up Level Delay
Time]
to start the system. This level also sets the wake up level when the drive is in Sleep Mode.
When
Y1-04 < 0
, the feedback level must decrease this amount to less than the setpoint.
0.0
(-999.9 - +999.9)
Note:
•
When PID operates in reverse mode, the feedback value must increase to more than the start level for the time set in
Y1-05
for the system to
start.
•
When
Y2-01 = 5 [Sleep Level Type = Output Frequency (non-PID)]
, the drive will ignore this parameter.
•
Set this parameter to 0.0 to disable the function.
•
Range is 0.00 to 99.99 with sign-bit
“
-
”
or
“
+
”
indicating Delta to Setpoint.
•
Display unit and scaling change when the system units change.
■
Y1-05: Sleep Wake-up Level Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
Y1-05
(3C04)
RUN
Sleep Wake-up Level Delay
Time
Sets the drive to start the System again when the feedback decreases to less than
Y1-04 [Sleep Wake-
up Level]
for the time set in this parameter.
1 s
(0 - 3600 s)
■
Y1-06: Minimum Speed
No.
(Hex.)
Name
Description
Default
(Range)
Y1-06
(3C05)
RUN
Minimum Speed
Sets the minimum frequency at which the drive will run. The drive applies this setting to HAND and
AUTO modes.
0.0 Hz
Determined by Y1-07
Note:
The unit, decimal place, and setting range change when the
Y1-07 [Minimum Speed Units]
setting changes:
•
Y1-07 = 0 [Hz]
: The setting range is 0.0 Hz to
E1-04
Hz.
•
Y1-07 = 1 [RPM]
: The setting range is 0 RPM to (
E1-04
× 60) RPM.
■
Y1-07: Minimum Speed Units
No.
(Hex.)
Name
Description
Default
(Range)
Y1-07
(3C06)
Minimum Speed Units
Sets the units and decimal place for
Y1-06 [Minimum Speed]
.
0
(0, 1)
0 : Hz
1 : RPM
Note:
Changing
Y1-07
will set
Y1-06 [Minimum Speed]
to the default value.
■
Y1-08: Low Feedback Level
No.
(Hex.)
Name
Description
Default
(Range)
Y1-08
(3C07)
RUN
Low Feedback Level
Sets the lower detection level for the PID feedback.
0.00%
(0.00 - 99.99%)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...