412
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
Y1-40: Maximum Speed
No.
(Hex.)
Name
Description
Default
(Range)
Y1-40
(3C27)
RUN
Maximum Speed
Sets the maximum speed.
0.0 Hz
(0.0 - 416.0)
Note:
This parameter is not effective when
Y1-40 = 0.0 Hz
or
Y1-40
>
E1-04 [Maximum Output Frequency]
×
d2-01 [Frequency Reference Upper
Limit]
.
◆
Y2: PID Sleep and Protection
■
Sleep Function
The Sleep Function uses the monitor data set in
Y2-01 [Sleep Level Type]
to know if the drive is necessary in the
system and turn off the drive.
This function helps to save the energy and prevent the deterioration on the motor.
*1
When
Y2-01 = 5 [Output Frequency (non-PID)]
, the drive will ignore the Start Level set in
Y1-04 [Sleep Wake-
up Level]
. Set
Y2-02
> 0 to enable the Sleep Function. The drive will enable the Sleep Function regardless of the
b5-01
setting or the status of the MFDI set for
H1-xx = 19 [PID Disable]
.
Sleep Activation Level and Sleep Level
•
Sleep Activation Level:
This level sets when the Sleep Function should start operation. You can use
Y2-04 [Sleep Activation Level]
or
Minimum Speed (the largest value from
d2-02
,
Y1-06
, and
Y4-12
) to set this level.
When the output frequency increases to more than the Sleep Activation Level, the Sleep Function will start to
monitor the system.
•
Sleep Level:
This is the level that the drive uses to go to sleep (stop). You can use
Y2-02 [Sleep Level]
or Minimum Speed to set
this level.
Delta to Setpoint Entry for Sleep Wake-up Level
Delta to Setpoint Entry lets you set
Y1-04 [Sleep Wake-up Level]
relative to the current setpoint and set a PID setpoint
when PID is not active.
Parameter/Condition
Delta Entry
Absolute Entry
Y1-04
b5-09 = 0 [PID Output Level Selection = Normal Output (Direct Acting)]
-0.00 to -99.99
0.00 to 99.99
Y1-04
b5-09 = 1 [Reverse Output (Reverse Acting)]
+0.00 to +99.99
0.00 to 99.99
Table 5.66 Absolute Mode and Delta to Setpoint Mode
Entry Mode
Keypad Display
Description
Absolute
The value set for
Y1-04
represents the feedback level that will wake-up the drive. You can
set
Y1-04
as an absolute value.
Delta to Setpoint
When the left-most digit changes to a Δ (delta), you can set a Sleep Wake-up Level relative
to the setpoint.
The effective Wake-up Level changes when
b5-09
changes:
•
b5-09 = 0
:
“
Setpoint -
Y1-04
”
•
b5-09 = 1
:
“
Se
Y1-04
”
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...