7.4 208 V Enclosed Model Specifications
534
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
*1
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
*3
Carrier frequency is 5 kHz. You must derate the current to increase the carrier frequency.
Table 7.7 208 V Enclosed Ratings
Model
D088
D114
D143
D169
D211
D273
Maximum Applicable Motor Output
(HP)
30
40
50
60
75
100
Input
Rated Input Current (A)
90.4
116.4
145.4
171.4
212.4
275.4
Rated Voltage
Rated Frequency
Three-Phase 208 Vac 50/60 Hz
Allowable Voltage
Fluctuation
-15 to 10%
Allowable Frequency
Fluctuation
±5%
Output
Rated Output Current (A)
88
114
143
169
211
273
Minimum Applicable
Motor Current (A)
15
15
30
30
30
45
Overload Tolerance
110% of rated output current for 60 s
150% peak
Carrier Frequency
User adjustable between 1 and 12.5 kHz
(Maximum Frequency varies with Rated Output Capacity)
Maximum Output Voltage
(V)
Three-Phase 208 Vac
Maximum Output
Frequency (Hz)
240 Hz
Harmonics
Reduction
Input Power (kVA)
Built-in
EMC
Filter (IEC/EN 61800-3
Category 2)
Built-in
*1
The maximum applicable motor output is based on 4-pole, general-purpose 220 V motor ratings. The rated output current of the drive
output amps must be equal to or more than the motor rated current.
*2
The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output current of
the drive output amps must be equal to or more than the motor rated current.
*3
Carrier frequency is 5 kHz. You must derate the current to increase the carrier frequency.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...