YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
83
Table 3.4 Output and Control Wiring
Model
H6BP
Motor Wiring
Standard Motor Terminal
Block TB1
Ground Wiring
Control Wiring
AWG,
kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
A1
Terminal Blocks
TB1, TB3-TB6
A1
Terminal Block
TB2 (FE)
A2
Terminal Blocks
TB1-TB4 and TB6
AWG, kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
AWG, kcmil
Tightening
Torque
(in lb)
B001
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B002
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B003
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B004
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B007
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B011
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B014
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B021
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B027
14-2
32
14-10, 8, 6-4, or
2
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B034
14-2
32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B040
14-2
32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B052
14-2
32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B065
14-2
32
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
B077
6-2/0
120
14-10, 8, 6-4, or
2-1/0
35, 40, 45, or 50
24-16
4.4 to 5.3
8.85 to 10.62
26-14
4
*1
24-16 is acceptable for solid wire or ferrule use only.
■
208 V Enclosed Wire Gauges and Torques
Table 3.5 Input Wiring
Model
H6BP
Standard Non-Fused
Input Disconnect Switch S1
With Option PM
Circuit Breaker CB1
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
Current Rating
Amps
AWG, kcmil
Tightening Torque
(in lb)
D002
20
14-8
19
15
14-10 or 8-3/0
50 or 120
D003
20
14-8
19
15
14-10 or 8-3/0
50 or 120
D004
20
14-8
19
15
14-10 or 8-3/0
50 or 120
D007
20
14-8
19
20
14-10 or 8-3/0
50 or 120
D010
20
14-8
19
25
14-10 or 8-3/0
50 or 120
D016
20
14-8
19
40
14-10 or 8-3/0
50 or 120
D024
45
10, 8, or (6-2)
35, 40, or 50
60
14-10 or 8-3/0
50 or 120
D030
63
10, 8, or (6-2)
35, 40, or 50
70
14-10 or 8-3/0
50 or 120
D046
100
8-2/0
200
110
14-10 or 8-3/0
50 or 120
D059
100
8-2/0
200
125
14-10 or 8-3/0
50 or 120
D074
115
8-2/0
200
150
14-10 or 8-3/0
50 or 120
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...