3 Receiving and System Components
YASKAWA
TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL
9
◆
Factory Set Parameters
Table 3.2 Factory Set HV600 Bypass (Redundant Drive) Parameters
Parameter
Value
Unit
Description
b1-08
1
–
Run Command Selection in Programming Mode = Accept RUN while Programming.
b3-01
1
–
Speed Search Selection at Start = Enabled
b3-05
3.0
sec.
Speed Search Delay Time
d1-01
10.0
Hz
Frequency Reference 1 (HAND Mode)
d2-01
–
%
Frequency Reference Upper Limit (Must be set by user)
d2-02
–
%
Frequency Reference Lower Limit (Must be set by user)
E1-01
480
V
Input Voltage Setting
E1-04
–
Hz
Maximum Output Frequency (Must be set by user)
E1-05
460
V
Maximum Output Voltage Setting
E2-01
–
Amps
Motor Rated Current (FLA) (Must be set by user)
H1-05
6E
–
Terminal Sx Function Selection = HAND Command
ON : HAND Mode
OFF : OFF Mode or AUTO Mode
H1-06
18
–
Terminal Sx Function Selection = Timer Function
H1-07
6D
–
Terminal Sx Function Selection = AUTO Command
ON : AUTO Mode
OFF : OFF Mode or HAND Mode
H2-01
0
–
Term M1-M2 Function Selection = During Run
ON : Drive is running
OFF : Drive is stopping
H2-02
12
–
Term M3-M4 Function Selection = Timer Output
H3-03
0.0
%
Terminal A1 Gain Setting
H3-09
2
–
Terminal A2 Signal Level Selection = 4 to 20 mA
L4-05
0
–
Frequency Reference Loss Detection Selection = Stop
L5-01
10
–
Number of Auto-Restart Attempts
L5-03
5.0
sec.
Time to Continue Making Fault Restarts (Time Between Auto Restart Attempts)
o3-02
1
–
Copy Allowed Selection = Enabled
S5-01
1
–
HAND Frequency Reference Selection =
S5-05
S5-04
1
–
HAND-OFF-AUTO Behavior = Normal
S5-05
10
Hz
HAND Frequency Reference 1
S5-07
0
–
HAND Key Function Selection = Disabled