3 Receiving and System Components

YASKAWA

TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL

9

Factory Set Parameters

Table 3.2 Factory Set HV600 Bypass (Redundant Drive) Parameters

Parameter

Value

Unit

Description

b1-08

1

Run Command Selection in Programming Mode = Accept RUN while Programming.

b3-01

1

Speed Search Selection at Start = Enabled

b3-05

3.0

sec.

Speed Search Delay Time

d1-01

10.0

Hz

Frequency Reference 1 (HAND Mode)

d2-01

%

Frequency Reference Upper Limit (Must be set by user)

d2-02

%

Frequency Reference Lower Limit (Must be set by user)

E1-01

480

V

Input Voltage Setting

E1-04

Hz

Maximum Output Frequency (Must be set by user)

E1-05

460

V

Maximum Output Voltage Setting

E2-01

Amps

Motor Rated Current (FLA) (Must be set by user)

H1-05

6E

Terminal Sx Function Selection = HAND Command

ON : HAND Mode

OFF : OFF Mode or AUTO Mode

H1-06

18

Terminal Sx Function Selection = Timer Function

H1-07

6D

Terminal Sx Function Selection = AUTO Command

ON : AUTO Mode

OFF : OFF Mode or HAND Mode

H2-01

0

Term M1-M2 Function Selection = During Run

ON : Drive is running

OFF : Drive is stopping

H2-02

12

Term M3-M4 Function Selection = Timer Output

H3-03

0.0

%

Terminal A1 Gain Setting

H3-09

2

Terminal A2 Signal Level Selection = 4 to 20 mA

L4-05

0

Frequency Reference Loss Detection Selection = Stop

L5-01

10

Number of Auto-Restart Attempts

L5-03

5.0

sec.

Time to Continue Making Fault Restarts (Time Between Auto Restart Attempts)

o3-02

1

Copy Allowed Selection = Enabled

S5-01

1

HAND Frequency Reference Selection =

S5-05

S5-04

1

HAND-OFF-AUTO Behavior = Normal

S5-05

10

Hz

HAND Frequency Reference 1

S5-07

0

HAND Key Function Selection = Disabled

Summary of Contents for H6R B Series

Page 1: ...YA I H 6 R 0 1 M O D E L S H6RxBxxx Three Phase 480 V 3 to 250 HP A C D R I V E F O R H VA C F A N P U M P A P P L I C AT I O N S R E D U N D A N T D R I V E O P E R AT I O N A L T E S T M A N U A L...

Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPYAIH6R01B HV600 REDUNDANT DRIVE OPERATIONAL TEST MANUAL...

Page 3: ...mental Safety Information 4 General Safety 4 2 Product Overview 5 How to Read Redundant Drive Catalog Codes 6 Models H6RxBxxx 7 3 Receiving and System Components 7 4 Primary Operation Tests 10 Primary...

Page 4: ...manual and the standard drive manuals General Safety General Precautions Some figures in the instructions include options and drives without covers or safety shields to more clearly show the inside o...

Page 5: ...dant Drive Package is engineered for use in critical HVAC building automation applications that require continuous reliable motor control This document provides a procedure to test the operation of th...

Page 6: ...Drive Catalog Codes Use the information in Figure 2 1 and Table 2 2 to read the catalog codes Figure 2 1 Catalog Code Table 2 2 Catalog Code Details No Description 1 HV600 Redundant Drive 2 Enclosure...

Page 7: ...3 34 4 180 180 150 240 240 200 Contact Yaskawa 302 302 250 1 Horsepower rating is based on standard NEMA B 4 pole motor design as represented in NEC table 430 150 Full Load Current Three Phase Altern...

Page 8: ...PLY 24VDC 150 mA MAX P OPTION CARD SHIELD GND FE COMMUNICATIONS INPUT R COMMUNICATIONS INPUT R COMMUNICATIONS OUTPUT S COMMUNICATIONS OUTPUT S JUMPER SH1 to 122 SH1 from 124 RUNNING DRIVE ON POWER FAU...

Page 9: ...d Current FLA Must be set by user H1 05 6E Terminal Sx Function Selection HAND Command ON HAND Mode OFF OFF Mode or AUTO Mode H1 06 18 Terminal Sx Function Selection Timer Function H1 07 6D Terminal S...

Page 10: ...10 22 TB1 1SN 138 127 127 to 125 127 from 129 127 128 128 to 125 128 from 129 128 RUNNING DRIVE ON POWER FAULT DRIVE AGREE 1 SPEED RUN FWD S1 RUN REV S2 EXTERNAL FAULT N O S3 FAULT RESET S4 HAND MODE...

Page 11: ...if necessary set min max speeds and accel decel times etc 11 When commissioning is complete set the HAND OFF AUTO switch to OFF to stop the drive Expanded Function Test Table 4 3 Expanded Function Te...

Page 12: ...rt Drive A 19 Confirm that you can use the BAS to change the speed reference for Drive A and Drive B 20 If necessary remove the front cover from Drive A to access the TB3 and TB4 terminal blocks below...

Page 13: ...TIONAL TEST MANUAL 13 Revision History Date of Publication Revision Number Revised Content April 2023 2 Revision Applicable Documents and Catalog Code February 2023 1 Revision Document title Addition...

Page 14: ...yaskawa eu com www yaskawa eu com YASKAWA EL TRICO DO BRASIL LTDA 777 Avenida Piraporinha Diadema S o Paulo 09950 000 Brasil Phone 55 11 3585 1100 Fax 55 11 3585 1187 www yaskawa com br In the event t...

Reviews: