112
YASKAWA
TOEPC71061732E HV600 Drive Installation & Primary Operation
Code
Name
Causes
Possible Solutions
oPE03
Multi-Function Input Setting Err
The settings for these parameters do not agree:
•
H1-01 to H1-07 [Terminals S1 to S7 Function
Selection]
•
H7-01 to H7-04 [Virtual Multi-Function Inputs 1
to 4]
Correct the parameter settings.
oPE05
Run Cmd/Freq Ref Source Sel Err
The setting to assign the Run command or frequency
reference to an option card is incorrect.
Correct the parameter settings.
oPE07
Analog Input Selection Error
The settings for
H3-02 and H3-10 [MFAI Function
Selection]
and
H7-30 [Virtual Analog Input
Selection]
overlap.
Set
H3-02, H3-10, and H7-30
correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
•
Setting value
0 [Frequency Reference]
•
Setting values
F and 1F [Not Used]
oPE08
Parameter Selection Error
You set a function that is not compatible with the
control method set in
A1-02 [Control Method
Selection]
.
1.
Push
to show
U1-18 [oPE Fault Parameter]
, and find
parameters that are not in the applicable setting range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
oPE09
PID Control Selection Fault
These parameters are set at the same time:
•
b5-01 = 1
•
b5-11 = 1 [PID Output Reverse Selection =
Negative Output Accepted]
And one of these parameters is set:
•
d2-02 ≠ 0.0 [Frequency Reference Lower Limit ≠
0.0%]
•
Y1-06 ≠ 0.0 [Minimum Speed ≠ 0.0%]
•
Y4-12 ≠ 0.0 [Thrust Frequency ≠ 0.0%]
•
Y1-01 ≠ 0 [Multiplex Mode ≠ Drive Only]
•
YF-01≠ 0 [PI Aux Control Selection ≠ Disabled]
Correct the parameter settings.
oPE10
V/f Data Setting Error
The parameters that set the V/f pattern do not satisfy
these conditions:
•
For motor 1:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
•
For motor 2:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Set the parameters correctly to satisfy the conditions.
oPE11
Carrier Frequency Setting Error
These parameters are set at the same time:
•
C6-05 > 6 [Carrier Freq Proportional Gain > 6]
•
C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When
C6-05 < 7
,
C6-04
becomes disabled.
C6-
03
stays active.
Set
C6-02 to C6-05
correctly.
oPE16
Energy Saving Constants Error
The Energy Saving parameters are not set in the
applicable setting range.
Make sure that
E5-xx
is set correctly as specified by the motor
nameplate data.
oPE33
Digital Output Selection Error
These two parameters are set at the same time:
•
H2-60 ≠ F [Term M1-M2 Secondary Function ≠
Not Used]
•
H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
Clear the
H2-01 to H2-03 = 1xx [Inverse output of xx]
settings.
Note:
It is not possible to set
H2-01 to H2-03 = 1xx [Inverse output of
xx]
when using output functions for logic operations (
H2-60,
H2-63, H2-66 ≠ F
).
oPE34
HAND/OFF/AUTO Input Setting
When
S5-04 = 0 [HAND-OFF-AUTO Behavior =
Legacy]
,
H1-xx = 6D and 6E [MFDI Function
Selection = AUTO Command and HAND Command]
are set at the same time.
Set only one of the two functions
H1-xx = 6D or 6E
.
oPE35
Network PI Aux Operation Mode
These parameter settings are not compatible:
•
Y9-50 ≠ 0 [PI Auxiliary Control Source ≠ Analog
Only]
•
Y9-51 = 1 [PI Aux Control Turn-Off Method =
Enabled]
Examine the settings for
Y9-50
and
Y9-51
.