YASKAWA
TOEPC71061732E HV600 Drive Installation & Primary Operation
49
No.
Name
Function
H
Left Arrow Key
Moves the cursor to the left.
Up Arrow Key/Down Arrow Key
/
•
Scrolls up or down to display the next item or the previous item.
•
Selects parameter numbers, and increments or decrements setting values.
Right Arrow Key (RESET)
•
Moves the cursor to the right.
•
Continues to the next screen.
•
Clears drive faults.
ENTER Key
•
Enters parameter values and settings.
•
Selects menu items to move the user between keypad displays.
•
Selects each mode, parameter, and set value.
I
AUTO Key
Sets drive operation to AUTO Mode.
The drive uses the
b1-01 [Frequency Reference Selection 1]
and
b1-02 [Run Command Selection 1]
settings.
Note:
Push
on the keypad to set the drive to HAND Mode before you use the keypad to operate the motor.
J
USB Terminal
Insertion point for a mini USB cable. Uses a USB cable (USB standard 2.0, type A - mini-B) to connect the keypad to a PC.
K
RJ-45 Connector
Uses an RJ-45 8-pin straight through UTP CAT5e extension cable or keypad connector to connect to the drive.
L
Clock Battery Cover
Cover for the clock battery.
Note:
•
The battery included with the keypad is for operation check. It may be exhausted earlier than the expected battery life
described in the manual.
•
Refer to
“
Maintenance & Troubleshooting Manual (TOEPYAIHV6001)
”
for more information about replacement
procedure.
To replace the battery, use a Hitachi Maxell
“
CR2016 Lithium Manganese Dioxide Lithium Battery
”
or an equivalent battery
with these properties:
•
Nominal voltage: 3 V
•
Operating temperature range: -20 °C to +85 °C (-4 °F to +185 °F)
M
Insulation Sheet
An insulating sheet is attached to the keypad battery to prevent battery drain. Remove the insulation sheet before you use the
keypad for the first time.
*1
Refer to
AUTO LED and HAND LED Indications on page 49
for more information about AUTO LED and HAND LED indications.
◆
AUTO LED and HAND LED Indications
Table 8.2 AUTO LED and HAND LED Indications
AUTO LED
HAND LED
Status
OFF
OFF
OFF Mode
OFF
ON
HAND Mode
OFF
Long blink (50% duty)
HAND Mode
•
When the Frequency Reference is 0 or during deceleration
•
During PI Sleep
OFF
Double blink
HAND Mode
When you clear the Run command and enter the Run command again during the time set in
C1-02 [Deceleration Time 1]
ON
OFF
AUTO Mode
Long blink (50% duty)
OFF
AUTO Mode
•
When the Frequency Reference is 0 or during deceleration
•
During PI Sleep
Double blink
OFF
AUTO Mode
When an MFDI sends a Fast Stop signal to stop the drive