Related Parameters
No.
Parameter Name
Setting Values
A1-01
Access Level Selection
Default: 2
Range: 0 to 3
A1-03
Initialize Parameters
Default: 0
Range: 0 to 5550; 6008 to 6011; 7770
E2-01
Motor Rated Current
Default:
Min.: 10% of drive rated current
Max.: 200% of drive rated current
E2-04
Number of Motor Poles
Default: 2
Min.: 2
Max.: 48
P1-03
Feedback Device Scaling
Default: 145.0 PSI
Min.: 0.1
Max.: 6000.0
P1-11
High Feedback Level
Default: 0.0 PSI
Min.: 0.0
Max.: 6000.0
P1-06
Minimum Pump Speed
Default: 40.0 Hz
Min.: 0.0
Max.: [E1-04]
P1-04
Start / Draw Down Level
Default: 0.0
Min.: -999.9
Max.: 999.9
P2-02
Sleep Level
Default: 0.0 Hz
Min.: 0.0
Max.: 6000.0
P4-10
AUTO Mode Operator Run Power Down Storage
Default: 0
Range: 0, 1
P5-02
HAND Speed Reference 1
Default: 40.0 Hz
Min.: 0
Max.: [E1-04]
P5-04
HAND Key Function Selection
Default: 1
Range: 0, 1
Q1-01
PID Controller Setpoint 1
Default: 0.0
Min.: 0.0
Max.: 6000.0
U1-99
Anti-No-Flow Timer
No signal output available
4.5 iQpump Presets and Functions
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide
121
4
Start-Up Programming & Operation
Summary of Contents for iQpump1000
Page 355: ......