H3 Multi-Function Analog Input Settings
H3-
oo
Setting
Function
LCD Display
Description
Page
23
Water Level or Suction
Input
WaterLvl/Suction
When Water Level Control is enabled (Q4-01 = 1):
0 V or 4 mA = 0 (ft)
10 V or 20 mA = Q4-02 (PSI) * 2.308 ft/PSI OR
When Suction Pressure Control is enabled (Q5-01 = 1)
0 V or 4 mA = 9 (PSI)
10 V or 20 mA = Q5-02 (PSI) OR
When Vacuum Control is enabled (Q5-01 = 2)
0 V or 4 mA = 0 (”Hg)
10 V or 20 mA = Q5-02 (”Hg)
–
25
Secondary PI Setpoint
PI2 Setpoint
10 V = S3-02 (maximum output frequency)
–
26
Secondary PI Feedback PI2 Feedback
10 V = S3-02 (maximum output frequency)
–
pressure to be read in the drive.
pressure (or higher level of vacuum) to be read in the drive.
u
H4: Analog Outputs
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
H4-01
(041D)
Multi-Function Analog
Output Terminal FM
Monitor Selection
Term FM FuncSel
Selects the data to be output through multi-function analog
output terminal FM.
Set the desired monitor parameter to the digits available in
U
o
-
oo
.
For example, enter “103” for U1-03.
Default: 102
Range: 000 to
999
H4-02
(041E)
Multi-Function Analog
Output Terminal FM
Gain
Terminal FM Gain
Sets the signal level at terminal FM that is equal to 100% of the
selected monitor value.
Default: 100.0%
Min.: -999.9
Max.: 999.9
H4-03
(041F)
Multi-Function Analog
Output Terminal FM
Bias
Terminal FM Bias
Sets the signal level at terminal FM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
H4-04
(0420)
Multi-Function Analog
Output Terminal AM
Monitor Selection
Terminal AM Sel
Selects the data to be output through multi-function analog
output terminal AM.
Set the desired monitor parameter to the digits available in
U
o
-
oo
.
For example, enter “103” for U1-03.
Default: 103
Range: 000 to
999
H4-05
(0421)
Multi-Function Analog
Output Terminal AM
Gain
Terminal AM Gain
Sets the signal level at terminal AM that is equal to 100% of the
selected monitor value.
Default: 50.0%
Min.: -999.9
Max.: 999.9
H4-06
(0422)
Multi-Function Analog
Output Terminal AM
Bias
Terminal AM Bias
Sets the signal level at terminal AM that is equal to 0% of the
selected monitor value.
Default: 0.0%
Min.: -999.9
Max.: 999.9
H4-07
(0423)
Multi-Function Analog
Output Terminal FM
Signal Level Selection
Level Select1
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20mA
Default: 0
Range: 0 to 2
H4-08
(0424)
Multi-Function Analog
Output Terminal AM
Signal Level Selection
AO Level Select2
0: 0-10 VDC
1: -10 +10 VDC
2: 4-20 mA
0: 0 to 10 V
1: -10 to 10 V
2: 4 to 20 mA
Default: 0
Range: 0 to 2
B.7 H Parameters: Multi-Function Terminals
286
YASKAWA
TOEP YAIP1W 01A YASKAWA AC Drive - iQpump1000 Quick Start Guide