1 Applicable Machine Controllers
1.2.1 Mounting Optional Modules
16
1.2 Mounting/Removing Optional Modules on Machine Controller
Use the following procedure to mount or remove Optional Modules.
In the photos given here to explain the procedure, a Machine Controller MP2200 and an Optional Module 217-IF-01
are used. The procedure to mount an Optional Module AI-01 or AO-01 on a Machine Controller MP2300 or
MP2100M is the same as that to mount 217-IF-01 on MP2200.
1.2.1 Mounting Optional Modules
Use the following procedure to mount Optional Modules.
For the replacement of Optional Module, refer to
1.2.2 Removing Optional Modules
on page 1-18 to remove the
Optional Module to be replaced.
( 1 ) Preparation
1.
Backup the Programs
Save the programs written to the Machine Controller in the personal computer using MPE720. (Right-click the
Controller Folder, and select
Transfer
-
All Files
-
Dump
from the pop-up menu.)
2.
Remove the Machine Controller and Expansion Racks
a) For MP2300
Turn OFF the power supply and disconnect all the cables from the MP2300. Then, remove the MP2300 from the
panel or rack, and place it on a place with sufficient space, such as working table.
b) For MP2200 and MP2100M
Turn OFF the power supply and disconnect all the cables from the expansion rack (MP2200 base unit) where the
Optional Module to be replaced is mounted. Then remove the expansion rack and place it in a place with suffi-
cient space, such as working table.
( 2 ) Removing Optional Cover
Use the following procedure if the optional cover (JEPMC-OP2300) is installed on the slot.
1.
Remove the battery cover.
Pull the notch on the side of the MP2000 series towards you to remove the battery cover.