YASKAWA
TOBP C730600 29C YASKAWA AC Drive-Option LCD Operator Installation Manual
33
7 Related Parameters
7
Related Parameters
Parameters related to the use of the LCD Operator Option are listed below. Set these
parameters as needed for the application.
Table 11 Related Darameters
No.
Name
Description
Default
A1-00
Language
Selection
Language selection for the LCD Operator Option.
This parameter is not reset when the drive is initialized by parameter A1-
03.
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
0
b1-01
Frequency
Reference
Selection 1
Selects the source of the frequency reference.
0: Operator -Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus serial communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
b1-02
Run Command
Selection 1
Selects the run command input source.
0: Operator -RUN and STOP keys on the LCD Operator Option
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus serial communications
3: Option PCB
1
b1-15
Frequency
Reference 2
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus serial communications
3: Option PCB
4: Pulse Input (Terminal RP)
0
b1-16
Run Command
Source 2
Selects the Run command input source.
0: Operator - RUN and STOP keys on the LCD Operator Option
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus serial communications
3: Option PCB
0
o2-01
LOCAL/
REMOTE Key
Function
Selection
Enables/Disables the LCD Operator Option LOCAL/REMOTE key.
0: Disabled
1: Enabled
1