TOBP C730600 35B YASKAWA AC Drive Option LED Operator Installation Manual
7 Related Parameters
7
Related Parameters
Parameters related to the use of the LED Operator Option are listed below. Set these
parameters as needed for the application.
The symbol “
{
” in the J1000 column indicates this parameter No. applies to the J1000
drive. The symbol “
{
” in the A1000, V1000 column indicates this parameter No. applies to
A1000 and V1000 drives.
Table 8 Related Parameters
No.
Name
Drive
Description
Default
J1000
A1000
x
V1000
b1-01
Frequency
Reference
Selection 1
{
{
Selects the source of the frequency reference.
0: Operator -Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus serial communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
b1-02
Run Command
Selection 1
{
{
Selects the run command input source.
0: Operator -RUN and STOP keys on the LED
Operator Option
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus serial communications
3: Option PCB
1
b1-15
Frequency
Reference 2
×
{
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus serial communications
3: Option PCB
4: Pulse Input (Terminal RP)
0
b1-16
Run Command
Source 2
×
{
Selects the Run command input source.
0: Operator - RUN and STOP keys on the LED
Operator Option
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus serial communications
3: Option PCB
0
o2-01
LOCAL/
REMOTE Key
Function
Selection
×
{
Enables/Disables the LED Operator Option LOCAL/
REMOTE key.
0: Disabled
1: Enabled
1
o2-02
STOP Key
Function
Selection
{
{
Enables/Disables the operator panel STOP key when
the drive is operated form external sources (not
operator).
0: Disabled
1: Enabled
1