Maintenance and inspection
9
-
58
9.2
Note on battery unit
9.2.1
Battery pack replacement
Fig. 9-3: Battery unit location
The battery units are installed as shown in picture "The location of the battery unit".
If battery alarm occuring in the robot controller, battery pack has to be changed in the
following form.
1. Turn the robot controller to the main power supply (see ).
Fig. 9-4: Main power switch in "switch-off" position
2. Remove the fixing screws from the cover plate.
3. Carefully pull out the battery pack from the base.
NOTICE
The absolute encoder data will be lost
Removing the battery pack, make sure you not to remove the plug from circuit board.
Fastening bolts of cover plate
Battery unit
Power input module
Circuit board
Main power switch in "switch-off" position
3
4
1
2
1
3
2
4
with power ON.
WARNING
Do not open the door
High Voltage
1
1