GENERAL OPERATION

10

GENERAL OPERATION

2/17/95- RD 3196-10

GENERAL

OPERATION

The PLC gateway is normally mounted and wired on a Yaskawa drive panel.
The gateway, however, can be mounted remotely by the customer.  In this case,
special consideration must be given to the 120 VAC power source for the
gateway power supply.  DO NOT connect the gateway power cord directly into
a wall outlet.  Instead, use an isolation transformer and tie one side of the
secondary to the nearest earth ground (the steel structure of the building is
usually a good choice).  The ground studs on the MicroTrac drive panels or
cabinets must also be connected directly to a solid earth ground in order to
assure that the gateway enclosure and the drive panels are at the same potential.
Improper grounding may cause erratic operation of the LAN.

The PLC gateway, when connected to the A-B 1771 remote I/O cable, is treated
as a remote I/O rack by the PLC.  From a PLC-5 the selected rack number can
be between 1 and 7 (inclusive).  From a PLC-3 the rack number can be between
0 and 7.  Note that the PLC gateway is configured as a rack on the remote I/O
link, and cannot be the same rack number as any other rack on the remote I/O
link.  If local racks are to be used, the rack number assigned to the PLC
gateway must be greater than the last local rack number.

The baud rate of the A-B 1771 remote I/O link is determined by the PLC.  A
DIP switch on the SmartMUX board selects the A-B 1771 link speed.  The
acceptable baud rates are 57.6K, 115.2K, and 230.4K.

A gateway uses one entire remote rack with the following capacity:

— 64 numerics PLC to MicroTrac in group 0, slot 0.
— 64 numerics MicroTrac to PLC in group 0, slot 0.
— 8 local logics (8 inputs or 8 outputs) in group 0, slot 1.
— 112 logics PLC to MicroTrac in groups 1-7.
— 112 logics MicroTrac to PLC in groups 1-7.

CAUTION

The gateway must be properly grounded.  When mounting, use star washers

that will cut into the metal of the gateway box to ensure proper earth ground.

.

Summary of Contents for MicroTrac Gateway

Page 1: ...ior consent Products which the Company consents to have returned shall be shipped prepaid f o b the Company s factory The Company cannot assume responsibility or accept invoices for unauthorized repai...

Page 2: ...Trasfer 17 PAC Considerations 20 TROUBESHOOTING JARC BOARD 22 TROUBLESHOOTING SmartMUX BOARD 23 TROUBLESHOOTING A B PLC 5 or PLC 3 23 PCDU TERMINAL OPERATION 24 Block 0 Gateway Set Up 25 Information...

Page 3: ...0 List of Tables Table Number Title Page 1 JARC Jumper Selection 3 2 JARC Board SW1 DIP Switch Positions 1 8 4 3 JARC Board SW1 DIP Switch Positions 9 11 4 4 JARC Board SW1 DIP Switch Position 12 5 5...

Page 4: ...d and a power supply The NEMA 1 enclosure contains the electronics with internal connections for AC power digital I O points and external connections for the MicroTrac LAN The initial setup is factory...

Page 5: ...switches on the SmartMUX board labeled SW1 and SW2 set the rack address and the baud rate for the communications Refer to Figure 2 Figure 2 SmartMUX Board J1 EPROM I O Rack Connector J2 PWR LED Red fo...

Page 6: ...1 fuse This fuse protects the 5V power to the PCDU Positions 1 through 8 of DIP switch SW1 determine the LAN node address Usually this address is set for 200 when the system has only one PLC gateway T...

Page 7: ...ble 2 JARC Board SW1 DIP Switch Positions 1 8 MICROTRAC SW1 DIP Switch Position LAN LSB MSB ADDRESS 1 2 3 4 5 6 7 8 200 X X X O X X O O 201 O X X O X X O O 202 X O X O X X O O 203 O O X O X X O O 204...

Page 8: ...ard LED Operation LED COLOR DESCRIPTION PWR RED ON when the JARC board has proper 5V power from the power supply The power LED should always be ON RECON YELLOW ON when a LAN reconfiguration occurs Eac...

Page 9: ...SW2 to select the rack address and baud rate The rack address must be consecutive between zero and seven inclusive and must match the rack address set on the JARC board The first DIP switch SW1 contr...

Page 10: ...Switch ON O Open switch Switch OFF Table 9 SmartMUX Board Watchdog Switch DIP Switch SW1 WATCHDOG Position 5 DISABLE WATCHDOG X ENABLE WATCHDOG O DEFAULT X Closed switch Switch ON O Open switch Switc...

Page 11: ...ddresses of the 8 I O points range from I XX0 10 to I XX0 17 for inputs and O XX0 10 to O XX0 17 for outputs where XX is the Gateway rack number octal These I O must be all inputs or all outputs Table...

Page 12: ...rt of the specification the SmartMUX board must meet A user must place a terminating resistor on both physical ends of a remote I O link to ensure proper operation NOTE Refer to Allen Bradley s 1785 P...

Page 13: ...ted as a remote I O rack by the PLC From a PLC 5 the selected rack number can be between 1 and 7 inclusive From a PLC 3 the rack number can be between 0 and 7 Note that the PLC gateway is configured a...

Page 14: ...I notation Thus LAN CHANNEL 124 INPUT RACK 2 GROUP 4 or I 24 LAN CHANNEL 127 INPUT RACK 2 GROUP 7 or I 27 The sub channel number will also be in octal and will directly correspond to the bit number of...

Page 15: ...number Thus LAN CHANNEL 015 OUTPUT RACK 1 GROUP 5 or O 15 The sub channel number will also be in octal and will directly correspond to the bit number of the simulated input Thus the 16 possible bits a...

Page 16: ...eading digit must be a 1 The SmartMUX board only supports Numeric block transfers to slot 0 and group 0 Thus LAN CHANNEL 130 RACK 3 GROUP 0 The PAC block s sub channel number will be in decimal and wi...

Page 17: ...umeric outputs except that the leading digit is always 0 The SmartMUX board only supports Numeric block transfers to slot 0 and group 0 Thus LAN CHANNEL 030 RACK 3 GROUP 0 The PAC block s sub channel...

Page 18: ...nit RDU or a personal computer TracView display The subsequent programming techniques make sure that a change from one device is reflected at the other device and establish when one device takes prece...

Page 19: ...d the same way The PLC initialization table refers to this RDCI by its function number 115 Figure 9 Sample PAC Diagram 300 E TO OTHER CIRCUITS IN THIS DRIVE S PAC DIAGRAM F 115 MASTER LINE SPD RDCI FC...

Page 20: ...e PLC gateway detects a change in data from the PLC the appropriate drive is updated with the new data The data transition initiates this exchange This new value is returned to the PLC as confirmation...

Page 21: ...locks with the decimal point DP parameter As shown in Figure 10 the DP for the pertinent NUMI block must be specified as 2 In some cases a 16 bit signed integer 32 768 may not be sufficient for the re...

Page 22: ...ue PLCTODSD Data transferred from the PLC to the Drive LOAD_PLC MOV 0 Move Source PLC_DATA 0 Dest PLCTODSD 0 NEQ MOV 1 Not Equal A B Move A DSDTOPLC Source DSDTOPLC 0 0 B DSDTOPLC_OLD Dest PLCTODSD 0...

Page 23: ...ions fit into the overall handling of drive setup parameters in the PAC diagram Just as the PLC initialization table allows the PLC to access drive setup parameters function number values the RDU init...

Page 24: ...e number which is usually 200 but could be 200 210 2 A decimal location is independently assigned in each row The SCDU PCDU RDU and PLC can each have different decimal locations 3 The PAC channel in t...

Page 25: ...reconfiguration A reconfiguration occurs when ever a new node enters the network During power up start up or initialization of any node on the network this LED will turn ON for approximately 1 second...

Page 26: ...odd rack address or twice if the node is an even rack address COMM GREEN When the Allen Bradley PLC establishes communication with LED1 the SmartMUX board this LED will flash or be ON A flashing COMM...

Page 27: ...row and ENT enter The diagnostic information is a circular list This display can be changed by pressing the INC or DEC keys Pressing the INC key displays the next line of information and pressing the...

Page 28: ...l This block displays the digital logic data read by the PLC from the remote I O rack simulated by this gateway This is shown by the abbreviation Dig Rd followed by the rack and group number a dash an...

Page 29: ...viation Dig Wr followed by the rack and group number a dash and the sixteen bit digital value displayed in hexadecimal representation Dig Wr Y0 Where Y is the unused rack number Dig Wr Y1 is the data...

Page 30: ...is shown by the abbreviation Blk Wr followed by the rack number a dash the element number within the block a dash and the sixteen bit value displayed in hexadecimal representation A block transfer co...

Page 31: ...his gateway This is logic data to be written to the gateway from the drive indicated by the node number The channel number agrees with the channel specified by the LOGO element LOGO NN CCC Where NN is...

Page 32: ...e diagnostic displays shows the NUMO memory allocations in this gateway This is numeric data to be written to the gateway from the drive indicated by the node number The channel number agrees with the...

Page 33: ...istered trademarks of the Allen Bradley Company Inc SmartMUX is a trademark of Western Reserve Controls Inc Yaskawa Electric 16555 W Ryerson Road New Berlin Wisconsin 53151 800 541 0939 262 782 0200 F...

Reviews: