4-1
173124-1CD
HW1482991
4
Wiring
4.1 Grounding
MPL300
II
4
Wiring
4.1
Grounding
Follow electrical installation standards and wiring regulations for
grounding. A ground wire of 5.5 mm
2
or more is recommended.
to connect the ground line directly to
the manipulator.
Fig. 4-1: Grounding Method
WARNING
•
Ground resistance must be 100
Ω
or less.
Failure to observe this warning may result in fire or electric shock.
•
Before wiring, make sure to turn the primary power supply off, and
put up a warning sign. (ex. DO NOT TURN THE POWER ON.)
Failure to observe this warning may result in fire or electric shock.
CAUTION
•
Wiring must be performed by authorized or certified personnel.
Failure to observe this caution may result in fire or electric shock.
•
DO NOT cover the cable with heat insulating material, and avoid
multiple cabling when laying manipulator cables from the
manipulator to the DX200.
Failure to observe this caution may result in burn caused by cable heat
emission failure.
NOTE
• Never use this wire sharing with other ground lines or
grounding electrodes for other electric power, motor
power, welding devices, etc.
• Where metal ducts, metallic conduits, or distributing racks
are used for cable laying, ground in accordance with
electrical installation standards.
A
Bolt M8 (for grounding)
Delivered with the manipulator
5.5 mm
2
or more
Enlarged View A