7 Transfer of Parameter Settings
YASKAWA America, Inc.
PL.GA500.01 YASKAWA AC Drive - V1000 to GA500 Transition Guide
35
0x0313 E2-06
Motor Leakage
Inductance
Sets the voltage drop due to motor leakage
inductance as a percentage of motor rated
voltage. This value is automatically set during
Auto-Tuning.
0.0~60.0
0.0~40.0
kVA
Depend
kVA
Depend
DEC %
0x031A E3-04 (FMAX)
Sets the maximum output frequency used for
motor 2.
40.0~590.0 40.0~400.0
A1-02,
O2-09,kVA
Depend
A1-02,
O2-09,kVA
Depend
DEC
O1-
04
0x031C E3-06
Motor 2 Base
Frequency (FA)
Sets the base frequency used for motor 2.
0.0~590.0
0.0~400.0
A1-02,
O2-09,kVA
Depend
A1-02,
O2-09,kVA
Depend
DEC
O1-
04
0x031D E3-07
Motor 2 Minimum
Output Frequency
(FB)
Sets the middle output frequency used for
motor 2.
0.0~590.0
0.0~400.0
A1-02,
O2-09,kVA
Depend
A1-02,
O2-09,kVA
Depend
DEC
O1-
04
0x031F E3-09
Motor 2 Minimum
Output Frequency
(FMIN)
Sets the minimum output frequency used for
motor 2.
0.0~590.0
0.0~400.0
A1-02,
O2-09,kVA
Depend
A1-02,
O2-09,kVA
Depend
DEC
O1-
04
0x0345 E3-11
Motor 2 Mid Output
Frequency 2
Used only for fine-tuning the V/f ratio within the
rated output range. This setting rarely needs to be
changed.
0.0~590.0
0.0~400.0
A1-02,
O2-09,kVA
Depend
A1-02,
O2-09,kVA
Depend
DEC
O1-
04
0x0324 E4-04 Motor 2 Motor Poles
Sets the number of poles of motor 2. This value
is automatically set during Auto-Tuning.
2~120
2~48
4
4
DEC
0x0326 E4-06
Motor 2 Leakage
Inductance
Sets the voltage drop due to motor leakage
inductance as a percentage of rated voltage of
motor 2. This value is automatically set during
Auto-Tuning.
0.0~60.0
0.0~40.0
kVA
Depend
kVA
Depend
DEC %
0x032C E5-04
Motor Poles (for PM
motor)
Sets the number of motor poles.
2~120
2~48
E5-01
Depend
E5-01
Depend
DEC
0x0381 F1-02
Operation Selection at
PG Open Circuit
(PGO)
Selects the motor operation when PGo [PG
Disconnect] is detected.
0: Ramp to stop
1: Coast to stop
2: Fast Stop (use C1-09)
3: Alarm only
4: No alarm display
0~4
0~3
1
1
DEC
0x03A5 F6-04
Trace Sampling from
Communications
Option Board
Sets the delay time until bUS [Option
Communication Error] issues are detected.
0.0~12.0
0.0~5.0
2.0
2.0
DEC sec
0x040B H2-01
Terminals MA, MB,
and MC Function
Selection (relays)
Terminals MA, MB, and MC Function Selection
(relays)
0x0~
0x1A7
0x0~0x192 0x00E
0x00E
HEX
0x040C H2-02
Terminals P1 Function
Selection (open-
collector)
Terminals P1 Function Selection (open-collector)
0x0~
0x1A7
0x0~0x192 0x000
0x000
HEX
0x040D H2-03
Terminals P2 Function
Selection (open-
collector)
Terminals P2 Function Selection (open-collector)
0x0~
0x1A7
0x0~0x192 0x002
0x002
HEX
0x042A H5-06
Drive Transmit Wait
Time
Set the delay time from when the drive receives
data to when the drive sends data.
0~65
5~65
5
5
DEC ms
0x0435 H5-09 CE Detection Time
Sets the time required to detect a
communications error. Adjustment may be need
when networking several drives.
0.0~25.0
0.0~10.0
2.0
2.0
DEC sec
Reg.
No.
Param.
No.
Name
Description
Setting Range
Initial Setting
Base Unit
GA500
V1000
GA500
V1000