Time
UP
S1-SC
S6-SC
OFF
OFF
d1-03
d1-01 (Enabled when b1-01 = 0)
L4-01
b2-01
OFF
DC Injection braking
ON
ON
ON
P2-PC
Holding brake
Fast/Slow
Output frequency
0
Frequency Detection 2
(H2-03
=
05)
Closed
Closed
Open
b6-02
b6-01
Input
Output
Figure 4.9 Holding Brake Time Chart
u
Setting 7: Preset 7
Table 4.15 Preset 7: Parameters and Settings
No.
Parameter Name
Default Setting
A1-02
Control Method Selection
0: V/f Control
b1-01
Frequency Reference Selection 1
0: Operator
C1-01
Acceleration Time 1
3.0 s
C1-02
Deceleration Time 1
3.0 s
C6-01
Drive Duty Selection
0: Heavy Duty
C6-02
Carrier Frequency Selection
2: 5 kHz
d1-01
Frequency Reference 1
6.0 Hz
d1-02
Frequency Reference 2
30.0 Hz
d1-03
Frequency Reference 3
60.0 Hz
H1-05
Multi-Function Digital Input Terminal S5
Function
3: Multi-Step Speed 1
H1-06
Multi-Function Digital Input Terminal S6
Function
4: Multi-Step Speed 2
H2-02
Terminals P1 Function Selection
37: During frequency output
L3-04
Stall Prevention Selection during
Deceleration
0: Disabled
L8-05
Input Phase Loss Protection Selection
4.5 Application Selection
YASKAWA ELECTRIC TOEP C710606 47A YASKAWA AC Drive – V1000 Quick Start Guide
103
4
Start-Up Programming & Operation