B.1
Parameter Table
No.
Name
Description
A1: Initialization Parameters
Use A1 parameters to configure the basic environment for drive operation.
A1-00
Language Selection
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
A1-01
Access Level Selection
0: Operation only
1: User Parameters (access to parameters selected by the user)
2: Advanced Access Level
A1-02
Control Method Selection
0: V/f Control without PG
2: Open Loop Vector (OLV)
5: PM Open Loop Vector (PM)
Note: 1.
Does not return to the default setting after initialization.
2.
If using Open Loop Vector Control (A1-02 = 2), then Auto-Tuning
must be performed again after the drive is initialized.
A1-03
Initialize Parameters
0: No Initialize
1110: User Initialize (First set user parameter values must be stored
using parameter o2-03)
2220: 2-Wire Initialization
3330: 3-Wire Initialization
5550: OPE04 Error Reset
A1-04
Password 1
Refer to V1000 Technical Manual for details.
A1-05
Password 2
Refer to V1000 Technical Manual for details.
A1-06
Application Preset
Refer to V1000 Technical Manual for details.
A1-07
DriveWorksEZ Function Selection
Refer to V1000 Technical Manual for details.
A2: User Parameters
Use A2 parameters to program the drive.
A2-01
to
A2-32
User Parameters, 1 to 32
Refer to V1000 Technical Manual for details.
A2-33
User Parameter Automatic
Selection
Refer to V1000 Technical Manual for details.
b1: Operation Mode Selection
Use b1 parameters to configure the operation mode.
b1-01
Frequency Reference Selection 1
0: Operator - Digital preset speed d1-01 to d1-17.
1: Terminals - Analog input terminal A1 or A2.
2: Memobus communications
3: Option PCB
4: Pulse Input (Terminal RP)
B.1 Parameter Table
168