2.5 Wiring
DANGER!
Consider strain relief of the supply lines!
Since the plug for the supply lines of the input voltage has no (double)
insulation, not permanently fixed supply lines must be relieved from push
and pull!
CAUTION!
Consider temperature for external cables!
Cables may experience temperature increase due to system heat dissi-
pation. Thus the cabling specification must be chosen 25°C above
ambient temperature!
CAUTION!
Separate insulation areas!
The system is specified for SELV/PELV environment. Devices, which are
attached to the system must meet theses specifications. Installation and
cable routing other than SELV/PELV specification must be separated
from the system’s equipment!
2.5.1 Wiring power supply
For wiring the power supply has removable connectors. With the wiring of the connectors
a "push-in" spring-clip technique is used. This allows a quick and easy connection of your
supply lines. The clamping off takes place by means of a screwdriver.
U
max
240V AC / 30V DC
I
max
2A
Cross section
0.2 ... 1.5mm
2
(AWG 24 ... 16)
Stripping length 10mm
Use for wiring rigid wires respectively use wire sleeves. When using stranded wires you
have to press the release button with a screwdriver during the wiring.
1
Labeling on the casing
2
Release area
3
Connection hole for wire
4
Pin 1 of the connector is labelled by a white line.
Connectors
Data
Wiring procedure
VIPA System MICRO
Basics and mounting
Wiring > Wiring power supply
HB400 | PS | M07-2BA00 | en | 20-02