3 Electrical Installation
YASKAWA ELECTRIC
TOEP C710656 09D YASKAWA Power Regenerative Unit - R1000 Quick Start Guide
15
Wiring Specification
Main Circuit
Use the EMC filters and input fuses listed in the table below when wiring the main circuit. Make sure not to exceed the
given tightening torque values.
Table 6 Wiring Specification and Input Fuses
CE Standards Compliance for DC Power Supply Input
Factory Recommended Branch Circuit Protection
Install appropriate input fuses to the input side to protect regenerative unit wiring and prevent other secondary damage.
Select fuses according to
.
Refer to the Technical Manual for details on the regenerative unit Input Current and Rated Output Current.
NOTICE:
If a fuse is open or a Residual Current Device (RCD) is tripped, check the wiring and the selection of peripheral devices to
identify the cause. Contact Yaskawa before restarting the regenerative unit or the peripheral devices if the cause cannot be identified.
Model
Main Circuit
Recom. Cable (mm
2
)
Fuse
R/L1,
S/L2,
T/L3
,
r1/ 11,
1/ 21,
t1/ 31
Model
Rating
Ampere (A)
Fuse Holder
Manufacturer
2A03P5
4
4
2.5
4
350GH-20ULTC
20
HT4017
HINODE
2A0005
4
4
2.5
4
350GH-25ULTC
25
HT4017
HINODE
2A0007
4
4
2.5
4
350GH-32ULTC
32
HT4017
HINODE
2A0010
4
16
2.5
4
350GH-50ULTC
50
HT4017
HINODE
2A0014
6
16
2.5
6
350GH-63ULTC
63
HT4017
HINODE
2A0017
10
16
2.5
10
350GH-80ULTC
80
HT4017
HINODE
2A0020
10
16
2.5
10
350GH-100ULTC
100
HT4017
HINODE
2A0028
16
25
2.5
16
350GH-125ULTC
125
HT5723
HINODE
2A0035
25
35
2.5
16
350GH-160ULTC
160
HT5723
HINODE
2A0053
50
70
2.5
25
350GH-200ULTC
200
HT5723
HINODE
2A0073
70
120
2.5
35
170M2620
350
170H1007
BUSSMANN
2A0105
95
×
2P
150
×
2P
2.5
70
170M3021
500
170H3003
BUSSMANN
4A03P5
4
4
2.5
4
660GH-16ULTC
16
HT6017
HINODE
4A0005
4
4
2.5
4
660GH-16ULTC
16
HT6017
HINODE
4A0007
4
4
2.5
4
660GH-16ULTC
16
HT6017
HINODE
4A0010
4
6
2.5
4
660GH-25ULTC
25
HT6017
HINODE
4A0014
4
6
2.5
4
660GH-40ULTC
40
HT6017
HINODE
4A0017
10
16
2.5
10
660GH-40ULTC
40
HT6017
HINODE
4A0020
10
16
2.5
10
660GH-50ULTC
50
HT6017
HINODE
4A0028
10
16
2.5
10
660GH-63ULTC
63
HT6017
HINODE
4A0035
10
16
2.5
10
660GH-80ULTC
80
HT6017
HINODE
4A0043
10
16
2.5
10
660GH-100ULTC
100
HT6017
HINODE
4A0053
16
25
2.5
16
660GH-125ULTC
125
HT7723
HINODE
4A0073
25
50
2.5
16
660GH-160ULTC
160
HT7723
HINODE
4A0105
50
70
2.5
25
170M1371
250
170H1007
BUSSMANN
4A0150
95
150
2.5
25
170M2620
350
170H1007
BUSSMANN
4A0210
95
×
2P
95
×
2P
2.5
95
170M3021
500
170H3003
BUSSMANN
4A0300
95
×
2P
120
×
2P
2.5
95
170M4016
630
170H3003
BUSSMANN
D1000R1000_QSG_E_conditional.book 15 ページ 2018年2月26日 月曜日 午後2時38分