10 UL Standards
56
YASKAWA ELECTRIC
TOEP C710656 09D YASKAWA Power Regenerative Unit - R1000 Quick Start Guide
Installing Standard Configuration Devices
NOTICE:
If a fuse is open or a Residual Current Device (RCD) is tripped, check the wiring and the selection of the peripheral devices.
Check the wiring and the selection of peripheral devices to identify the cause. Contact Yaskawa before restarting the regenerative unit
or the peripheral devices if the cause cannot be identified.
Recommended Branch Circuit Protection
Yaskawa recommends installing appropriate input fuses and fuse holders to the input side of the current suppression
reactor to maintain compliance with UL508C.
The fuses are listed in
Low Voltage Wiring for Control Circuit Terminals
Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The
external power supply shall be a UL Listed Class 2 power supply source or equivalent only.
Table 17 Control Circuit Terminal Power Supply
Regenerative Unit Short-Circuit Rating
This regenerative unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical
amperes, 240 Vac for 200 V class regenerative units and 480 Vac for 400 V class regenerative units, when protected by
fuses as specified on the
Connect the regenerative unit to an AC drive which has built-in semiconductor short-circuit protection and conforms to
UL short-circuit test.
4
0010
660GH-25ULTC 660 V, 25 A
HT6017
700 V, 75 A
HINODE
ACL-0030-EISC
-9353ABH
528 V, 30 A,
0.7 mH
300-057-280
528 V, 15 A,
0.4 mH
4
0014
660GH-40ULTC 660 V, 40 A
HT6017
700 V, 75 A
HINODE
ACL-0040-EISC
-9353ABH
528 V, 40 A,
0.53 mH
300-057-281
528 V, 25 A,
0.3 mH
4
0017
660GH-40ULTC 660 V, 40 A
HT6017
700 V, 75 A
HINODE
ACL-0050-EISC
-9353ABH
528 V, 50 A,
0.42 mH
300-057-281
528 V, 25 A,
0.3 mH
4
0020
660GH-50ULTC 660 V, 50 A
HT6017
700 V, 75 A
HINODE
ACL-0060-EISC
-9353ABH
528 V, 60 A,
0.36 mH
300-057-282
528 V, 30 A,
0.2 mH
4
0028
660GH-63ULTC 660 V, 63 A
HT6017
700 V, 75 A
HINODE
ACL-0080-EISC
-9353ABH
528 V, 80 A,
0.26 mH
300-057-283
528 V, 40 A,
0.15 mH
4
0035
660GH-80ULTC 660 V, 80 A
HT6017
700 V, 75 A
HINODE
ACL-0090-EISC
-9353ABH
528 V, 90 A,
0.24 mH
300-057-284
528 V, 50 A,
0.12 mH
4
0043
660GH-100ULTC 660 V, 100 A
HT6017
700 V, 75 A
HINODE
ACL-0120-EISC
-9353BH
528 V, 120 A,
0.18 mH
300-057-285
528 V, 60 A,
0.10 mH
4
0053
660GH-125ULTC 660 V, 125 A
HT7723
800 V, 100 A
HINODE
ACL-0150-EISC
-9353ABH
528 V, 150 A,
0.15 mH
300-057-286
528 V, 75 A,
0.08 mH
4
0073
660GH-160ULTC 660 V, 160 A
HT7723
800 V, 100 A
HINODE
ACL-0200-EISC
-9353ABH
528 V, 200 A,
0.11 mH
300-057-287
528 V, 100 A,
0.06 mH
4
0105
170M1371
700 V, 250 A
170H1007
1000 V,
400 A
BUSSMANN
ACL-0250-EISC
-9353ABH
528 V, 250 A,
0.09 mH
300-056-832
528 V, 161 A,
0.04 mH
4
0150
170M2620
700 V, 350 A
170H1007
1000 V,
400 A
BUSSMANN
ACL-0330-EISC
-9353ABH
528 V, 330 A,
0.06 mH
300-056-833
528 V, 237 A,
0.03 mH
4
0210
170M3021
700 V, 500 A
170H3003
1000 V,
630 A
BUSSMANN
ACL-0490-EISC
-9353ABH
528 V, 490 A,
0.04 mH
300-056-834
528 V, 326 A,
0.02 mH
4
0300
170M4016
700 V, 630 A
170H3003
1000 V,
630 A
BUSSMANN
ACL-0660-EISC
-9353ABH
528 V, 660 A,
0.03 mH
300-056-835
528 V, 466 A,
0.013 mH
Input/Output
Terminal Signal
Power Supply Specifications
Multi-function digital inputs
S1, S2, S3, S4, S5, S6, S7, S8,
SC, SN, SP
Use the internal LVLC power supply of the regenerative unit. Use class 2 for
external power supply.
Multi function analog inputs
+V, -V, A1, A2, A3, AC
Model
Three Phase Input Fuse
Three Phase Input AC
Reactor (3%L)
Three Phase Input AC
Reactor (1%L)
Fuse
Holder
SHANGHAI EAGTOP
ELECTRONIC TECHNOLOGY
CO LTD
Sao Electric Corporation
Model
Ratings
Model
Ratings
Manufacturer
Model
Ratings
Model
Ratings