5 Powering Up the Regenerative Unit
YASKAWA ELECTRIC
TOEP C710656 09D YASKAWA Power Regenerative Unit - R1000 Quick Start Guide
21
5
Powering Up the Regenerative Unit
Powering Up the Regenerative Unit
Review the following checklist before turning the power on.
Item to Check
Description
Power supply voltage
Check the power supply voltage.
200 V class: Three-phase 200 to 240 Vac 50/60 Hz
400 V class: Three-phase 380 to 480 Vac 50/60 Hz
Properly wire the power supply input terminals (R/L1, S/L2, and T/L3).
Properly wire the phase order of the power supply input terminals (R/L1, S/L2, and T/L3) and the
power supply voltage detection terminals (
).
Check for proper grounding of regenerative unit.
Regenerative unit output terminals
and drive terminals
Properly connect the DC voltage output terminals ( / ) on the regenerative unit to the DC power
supply input terminals ( / ) on the drive. Be particularly careful to correctly connect the and
terminals.
Control circuit terminals
Properly connect the control circuit terminals on the regenerative unit to other control devices.
Regenerative unit control terminal
status
Turn off the Run Commands for the regenerative unit and the peripheral control devices.
Power coordinating reactor, current
suppression reactor, and fuse
connections to regenerative unit
Properly connect the Power coordinating reactor, current suppression reactor, and fuse to
regenerative unit as shown in the Standard Connection Diagram.
r1/ 11, 1/ 21, and t1/ 31