8 Operation
8.4.8 Multiturn Limit Setting When Multiturn Limit Disagreement (A.CC) Occurred
8-36
8.4.8 Multiturn Limit Setting When Multiturn Limit Disagreement (A.CC) Occurred
Perform the following operation using the digital operator.
This operation can only be done when the A.CC alarm is generated.
Step
Display after
Operation
Key
Description
1
Press the DSPL/SET Key to select the utility function mode.
2
Press the LEFT/RIGHT or UP/DOWN Key or the UP or DOWN Key
to set the parameter Fn013.
*The digit that can be set will blink.
3
Press the DATA/ENTER Key. The display on the left will appear.
4
Press the DSPL/SET Key. The multiturn limit setting in the absolute
encoder will be changed.
When the setting is completed, “donE” will blink for about one second.
5
About one second
later
After “donE” is displayed, “PGSEt” will be displayed again.
6
Press the DATA/ENTER Key to return to the Fn013 display of the util-
ity function mode.
7
Turn OFF the power, and then turn it ON again to make the setting valid.
DSPL
SET
(DSPL/SET Key)
DATA
ENTER
(DATA/ENTER
Key)
DSPL
SET
(DSPL/SET Key)
DATA
ENTER
(DATA/ENTER
Key)