4 SERVOPACK Specifications and Dimensional Drawings
4-6
Installation
Follow the procedure below to install multiple SERVOPACKs side by side in a control panel.
SERVOPACK Orientation
Install the SERVOPACK perpendicular to the wall so the front panel containing connectors faces outward.
Cooling
As shown in the figure above, allow sufficient space around each SERVOPACK for cooling by cooling fans
or natural convection.
Side-by-side Installation
When installing SERVOPACKs side by side as shown in the figure above, allow at least 10 mm (0.39 in)
between and at least 50 mm (1.97 in) above and below each SERVOPACK. Install cooling fans above the
SERVOPACKs to avoid excessive temperature rise and to maintain even temperature inside the control
panel.
Environmental Conditions in the Control Panel
Ambient Temperature:0 to 40
°
C (32 to 104
°
F)
Humidity: 90
%
RH or less
Vibration: 9.8 m/s
2
Condensation and Freezing: None
Ambient Temperature for Long-term Reliability: 40
°
C (104
°
F) or less
Fan
Fan
30 mm
(1.18 in) min.
10 mm
(0.39 in) min.
50 mm (1.97 in) min.
50 mm (1.97 in) min.