3.3 FT82 SERVOPACK with MECHATROLINK-III Communications References
3.3.2 List of Alarms
3-102
*
These alarms are not stored in the alarm history. They are only displayed on the panel display.
Note: The A.Eb0, A.Eb2 to A.Eb9, and A.EC0 to A.EC2 alarms can occur when a Safety Module is connected.
Refer to the following manual for details.
AC Servo Drive
Σ
-V-Series/
Σ
-V-Series for Large-Capacity Models/
Σ
-7-Series User’s Manual Safety Module
(Manual No.: SIEP C720829 06)
A.E42
MECHATROLINK Station
Address Setting Error
The setting of the MECHATROLINK station
address is not correct.
Gr.2
No
A.E50
*
MECHATROLINK Syn-
chronization Error
A synchronization error occurred during
MECHATROLINK communications.
Gr.2
Yes
A.E51
MECHATROLINK Syn-
chronization Failed
Synchronization failed during MECHATROLINK
communications.
Gr.2
Yes
A.E60
*
Reception Error in
MECHATROLINK Commu-
nications
Communications errors occurred continuously
during MECHATROLINK communications.
Gr.2
Yes
A.E61
Synchronization Interval
Error in MECHATROLINK
Transmission Cycle
An error occurred in the transmission cycle
during MECHATROLINK communications.
Gr.2
Yes
A.E63
MECHATROLINK Syn-
chronization Frame Not
Received
Synchronization frames were continuously not
received during MECHATROLINK communica-
tions.
Gr.2
Yes
A.E71
Safety Option Module
Detection Failure
Detection of the Safety Option Module failed.
Gr.1
No
A.E72
Feedback Option Module
Detection Failure
Detection of the Feedback Option Module failed.
Gr.1
No
A.E74
Unsupported Safety
Option Module
An unsupported Safety Option Module was con-
nected.
Gr.1
No
A.Eb1
Safety Function Signal
Input Timing Error
An error occurred in the input timing of the safety
function signal.
Gr.1
No
A.EC8
Gate Drive Error 1
An error occurred in the gate drive circuit.
Gr.1
No
A.EC9
Gate Drive Error 2
An error occurred in the gate drive circuit.
Gr.1
No
A.Ed1
Command Execution Tim-
eout
A timeout error occurred for a MECHATROLINK
command.
Gr.2
Yes
A.F10
Power Supply Line Open
Phase
The voltage was low for more than one second
for phase R, S, or T when the main power supply
was ON.
Gr.2
Yes
A.F50
Servomotor Main Circuit
Cable Disconnection
The Servomotor did not operate or power was
not supplied to the Servomotor even though the
SV_ON (Servo ON) command was input when the
Servomotor was ready to receive it.
Gr.1
Yes
FL-1
*
System Alarm
An internal program error occurred in the SER-
VOPACK.
–
No
FL-2
*
FL-3
*
FL-4
*
FL-5
*
FL-6
*
CPF00
Digital Operator Commu-
nications Error 1
Communications were not possible between the
Digital Operator (model: JUSP-OP05A-1-E) and
the SERVOPACK (e.g., a CPU error occurred).
–
No
CPF01
Digital Operator Commu-
nications Error 2
Continued from previous page.
Alarm
Number
Alarm Name
Alarm Meaning
Servo-
motor
Stop-
ping
Method
Alarm
Reset
Possi-
ble?