4.5 FT83 SERVOPACKs with Analog Voltage/Pulse Train References
4-156
Pn425
2
Release Time for Torque
Limit at Main Circuit
Voltage Drop
0 to 1,000
1 ms
100
All
Immedi-
ately
Setup
*1
Pn426
2
Torque Feedforward
Average Movement
Time
0 to 5,100
0.1 ms
0
All
Immedi-
ately
Setup
*1
Pn427
2
Speed Ripple Compen-
sation Enable Speed
0 to 10,000
1 min
-1
0
Rotary Ser-
vomotor
Immedi-
ately
Tuning
*1
Pn456
2
Sweep Torque Refer-
ence Amplitude
1 to 800
1%
15
All
Immedi-
ately
Tuning
*1
Pn460
2
Notch Filter Adjustment
Selections 1
0000h to
0101h
–
0101h
All
Immedi-
ately
Tuning
*1
Pn475
2
Gravity Compensation-
Related Selections
0000h to
0001h
–
0000h
All
After
restart
Setup
*1
Pn476
2
Gravity Compensation
Torque
-1,000 to
1,000
0.1%
0
All
Immedi-
ately
Tuning
*1
Pn501
2
Zero Clamping Level
0 to 10,000
1 min
-1
10
Rotary
Immedi-
ately
Setup
*1
Pn502
2
Rotation Detection Level
1 to 10,000
1 min
-1
20
Rotary
Immedi-
ately
Setup
*1
Pn503
2
Speed Coincidence
Detection Signal Output
Width
0 to 100
1 min
-1
10
Rotary
Immedi-
ately
Setup
*1
Pn506
2
Brake Reference-Servo
OFF Delay Time
0 to 50
10 ms
0
All
Immedi-
ately
Setup
*1
Pn507
2
Brake Reference Out-
put Speed Level
0 to 10,000
1 min
-1
100
Rotary
Immedi-
ately
Setup
*1
Pn508
2
Servo OFF-Brake Com-
mand Waiting Time
10 to 100
10 ms
50
All
Immedi-
ately
Setup
*1
Pn509
2
Momentary Power Inter-
ruption Hold Time
20 to 50,000
1 ms
20
All
Immedi-
ately
Setup
*1
Continued on next page.
Continued from previous page.
Parameter
No.
Siz
e
Name
Setting
Range
Setting
Unit
Default
Setting
Applicable
Motors
When
Enabled
Classi-
fication
Refer-
ence
n.
X
Notch Filter Adjustment Selection 1
0
Do not adjust the first stage notch filter automatically during execution of auto-
tuning without a host reference, autotuning with a host reference, and custom
tuning.
1
Adjust the first stage notch filter automatically during execution of autotuning
without a host reference, autotuning with a host reference, and custom tuning.
n.
X
Reserved parameter (Do not change.)
n.
X
Notch Filter Adjustment Selection 2
0
Do not adjust the second stage notch filter automatically during execution of
autotuning without a host reference, autotuning with a host reference, and
custom tuning.
1
Adjust the second stage notch filter automatically during execution of autotun-
ing without a host reference, autotuning with a host reference, and custom
tuning.
n.X
Reserved parameter (Do not change.)
n.
X
Gravity Compensation Selection
0
Disable gravity compensation.
1
Enable gravity compensation.
n.
X
Reserved parameter (Do not change.)
n.
X
Reserved parameter (Do not change.)
n.X
Reserved parameter (Do not change.)