Sigma II User’s Manual
Chapter 7: Using the Digital Operator
7 - 26
Follow this procedure to automatically adjust the speed/torque reference offset.
Using the Hand-held Digital Operator
1.
Input the (intended) 0V reference voltage from the host controller or external
circuit.
2.
Press the
DSPL/SET
key to select the auxiliary function mode.
3.
Select the parameter Fn009.
Press the
Left Arrow
or
Right Arrow
key to select the digit.
Press the
Up Arrow
or
Down Arrow
key to change the value.
4.
Press the
DATA/ENTER
key, and the display will be as shown below.
5.
Press the
MODE/SET
key, and the following display will flash for one second.
The reference offset will be automatically adjusted.
6.
Press the
DATA/ENTER
key to return to the auxiliary function mode display.
This completes the speed/torque reference offset automatic adjustment.
Servomotor
Slow Rotation
(Servo ON)
Servo amplifier
Servo OFF
0V Speed or
Torque
Reference
Host
Controller
Flashing for
one second
Summary of Contents for SGMAH
Page 1: ...Sigma II Series Servo System User s Manual...
Page 2: ......
Page 4: ...ii This page intentionally left blank...
Page 6: ...iv This page intentionally left blank...
Page 10: ...Sigma II User s Manual Table of Contents Preface viii Notes...
Page 17: ...Sigma II User s Manual Table of Contents Preface xv C 6 Torque Control Mode C 9...
Page 18: ...Sigma II User s Manual Table of Contents Preface xvi...
Page 38: ...Sigma II User s Manual Chapter 2 Installation 2 10 NOTES...
Page 472: ...Sigma II User s Manual Appendix C Examples of Standard Connections C 10 Notes...
Page 487: ......