5.4 Special Wiring
5-19
5
5.4.5 AC/DC Reactor for Harmonic Suppression
(1) Reactor Types
The SGDS SERVOPACK has reactor connection terminals for power supply harmonic suppression. The type of
reactor to be connected differs depending on the SERVOPACK capacity. Refer to the following table.
Note: Select a proper AC or DC reactor for the input current to the SERVOPACK.
Refer to
2.5.2 Molded-case Circuit Breaker and Fuse Capacity
for input current to each
SERVOPACK. For the kind of reactor, refer to
4.4.12 AC/DC Reactors for Harmonic Suppression.
(2) Connecting a Reactor
Connect a reactor as shown in the following diagram.
Note: 1. The DC reactor’s
1 and
2 terminals are short-circuited before shipment. Remove the lead
wire between these two terminals and connect the DC reactor.
2. AC/DC reactor is an option.
Applicable
SERVOPACK Model
SGDS-
AC/DC Reactor
Model
Reactor Specifications
Impedance
(mH)
Rated
Current
(A)
Single-phase,
100 V
A5F
X5053
20.0
2.0
01F
02F
X5054
5.0
3.0
04F
X5056
2.0
5.0
Single-phase,
200 V
A5A
X5052
45.0
1.0
01A
02A
X5053
20.0
2.0
04A
X5054
5.0
3.0
08A
X5056
2.0
5.0
Three-phase,
200 V
10A
X5061
4.8
15A
X5060
1.5
8.8
20A
30A
X5059
1.0
14.0
AC Reactor
DC Reactor
SGDS
SERVOPACK
AC reactor
Power supply
L1
L2
SGDS
SERVOPACK
DC reactor
1
2