5 Wiring
5.1.1 Names and Descriptions of Main Circuit Terminals
5-2
5.1 Wiring Main Circuit
This section describes typical examples of main circuit wiring, functions of main circuit terminals, and the power
ON sequence.
5.1.1 Names and Descriptions of Main Circuit Terminals
• Do not bundle or run power and signal lines together in the same duct. Keep power and signal lines sepa-
rated by at least 30 cm (11.81 in).
• Use twisted-pair wires or multi-core shielded-pair wires for signal and encoder (PG) feedback lines.
The maximum length is 3 m (118.11 inches) for reference input lines and is 20 m (787.40 in) for PG feedback lines.
• Do not touch the power terminals for five minutes after turning power OFF because high voltage may still
remain in the SERVOPACK.
Make sure the charge indicator is out first before starting an inspection.
• Avoid frequently turning the power ON and OFF. Do not turn the power ON or OFF more than once per
minute.
Since the SERVOPACK has a capacitor in the power supply, a high charging current flows for 0.2 seconds when the
power is turned ON. Frequently turning power ON and OFF causes main power devices like capacitors and fuses to
deteriorate, resulting in unexpected problems.
Terminal
Symbol
Name
Description
L1, L2
or
L1, L2, L3
Main circuit input
terminal
50 W to 400 W
Single-phase 100 to 115 V
+10%
,
-15%
(50/60 Hz)
50 W to 400 W
Single-phase 200 to 230 V
+10%
,
-15%
(50/60 Hz)
750W
Single-phase 200 to 230 V
+10%
,
-15%
(50/60 Hz)
Note: Terminal L3 is not used. Do not connect.
500 W to 3.0 kW Three-phase 200 to 230 V
+10%
,
-15%
(50/60 Hz)
U, V, W
Servomotor
connection terminals
Connects to the servomotor.
L1C, L2C
Control power input
terminal
50 W to 400 W
Single-phase 100 to 115 V
+10%
,
-15%
(50/60 Hz)
50 W to 3.0 kW
Single-phase 200 to 230 V
+10%
,
-15%
(50/60 Hz)
Ground terminals (×2)
Connects to the power supply ground terminals and servomotor ground termi-
nal.
B1/
, B2
or
B1/ , B2, B3
External regenerative
resistor terminal
50 W to 400 W
Normally not connected.
Connect an external regenerative resistor (provided by cus-
tomer) between B1/
and B2 if the regenerative capacity
is insufficient.
Note: B3 terminal is not provided.
750 W to 3.0 kW
Normally short B2 and B3 (for an internal regenerative
resistor).
Remove the wire between B2 and B3 and connect an exter-
nal regenerative resistor between B1/
and B2 if the
capacity of the internal regenerative resistor is insufficient.
Customers must provide an external regenerative resistor
terminal.
1, 2
DC reactor
connection terminal
for power supply
harmonic suppression
750 W to 3.0 kW
Normally short
1-
2 .
If a countermeasure against power supply harmonic waves
is needed, connect a DC reactor between
1-
2
CAUTION
SIEPS80000025.book 2 ページ 2004年10月25日 月曜日 午前11時57分