background image

1 Preface and General Precautions

YASKAWA

TOEPC71061687B Powerlink Option Installation Manual

7

WARNING

Electrical Shock Hazard. Do not immediately energize the drive or operate peripheral

devices after the drive blows a fuse or trips an RCM/RCD. Wait for the time specified on the warning label at a
minimum and make sure that all indicators are OFF. Then check the wiring and peripheral device ratings to find
the cause of the problem. Contact Yaskawa before energizing the drive or peripheral devices if the cause is not
known. Failure to obey can cause death or serious injury and damage to the drive.

WARNING

Fire Hazard. Install sufficient branch circuit short circuit protection as specified by

applicable codes and this manual. The drive is suited for circuits that supply not more than 100,000 RMS
symmetrical amperes, 240 Vac maximum (200 V Class), 480 Vac maximum (400 V Class). Failure to obey can
cause death or serious injury.

CAUTION

Crush Hazard. Do not hold the drive by the front cover or terminal cover. Tighten the

screws correctly before moving the drive. Failure to obey can cause minor to moderate injury.

CAUTION

Burn Hazard. Do not touch a hot drive heatsink. De-energize the drive, wait 15 minutes

minimum, and make sure that the heatsink is cool to replace the cooling fans. Failure to obey can cause minor to
moderate injury.

NOTICE

Observe correct electrostatic discharge (ESD) procedures when touching the drive and

circuit boards. Failure to obey can cause ESD damage to the drive circuitry.

NOTICE

Do not connect or disconnect the motor from the drive while the drive is supplying voltage.

Incorrect equipment sequencing can cause damage to the drive.

NOTICE

Do not do a withstand voltage test or Megger test on the drive. Failure to obey can cause

damage to the drive.

NOTICE

Do not connect or operate damaged equipment or equipment with missing parts. Failure to

obey can cause damage to the drive and connected equipment.

NOTICE

Install fuses and an RCM/RCD. Failure to obey can cause damage to the drive.

NOTICE

Do not use unshielded wire for control wiring. Use shielded, twisted-pair wires and ground

the shield to the ground terminal of the drive. Failure to obey can cause electrical interference and unsatisfactory
system performance.

NOTICE

Do not allow unqualified personnel to use the product. Before you connect a dynamic

braking option to the drive, make sure that you review Braking Unit and Braking Resistor Unit Installation Manual
TOBPC72060001. Failure to obey can cause damage to the drive and braking circuit.

NOTICE

Make sure that all connections are correct after you install the drive and connecting

peripheral devices. Failure to obey can cause damage to the drive.

NOTICE

Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits.

Failure to obey can cause damage to the drive, phase-advancing capacitors, LC/RC noise filters, and leakage
breakers (ELCB, GFCI, or RCM/RCD).

Intended Use

This communication option card is electrical equipment intended to enable Yaskawa drives to
communicate with an additional fieldbus system for commercial use. Do not use this product for
any other purpose.

1.

Read and understand all safety precautions.

2.

Wire and ground the drive and communication option card in accordance with all
applicable standards and safety precautions.

3.

Firmly attach all parts and protective covers.

4.

Always use the product in the proper environmental conditions as specified in this manual.

DANGER

Electrical Shock Hazard. Make sure that all electrical connections are correct and install all

drive covers before energizing the drive. Use terminals for their intended function only. Incorrect wiring or ground
connections, and incorrect repair of protective covers can cause death or serious injury.

Summary of Contents for SI-EL3

Page 1: ...Powerlink Option Options Card for AC Drives and Regenerative Units Installation Manual Type SI EL3 SI EL3 V...

Page 2: ...This Page Intentionally Blank 2 YASKAWA TOEPC71061687B Powerlink Option Installation Manual...

Page 3: ...EDs 12 LEDs L A OUTand L A IN Ethernet Link Activity 1 and 2 12 S E LED 12 MS LED 13 Indicator Flash Rates 14 Connecting the Option Card 14 Communication Cable 15 Network Termination 15 5 Mechanical E...

Page 4: ...ooting 29 Communication Option Card Error Codes 29 Emergency Error Codes 30 Yaskawa specific SDO Abort Codes 37 Fault 38 Option Board Error Management 39 Minor Faults Alarms 40 8 Disposal 41 Disposal...

Page 5: ...to the final system design In all cases Yaskawa products should not be incorporated into a product or design as the exclusive or sole safety control function All control functions are designed to dyna...

Page 6: ...area around the drive motor and machine area and attach covers couplings shaft keys and machine loads before energizing the drive Failure to obey can cause death or serious injury WARNING Fire Hazard...

Page 7: ...NOTICE Do not connect or operate damaged equipment or equipment with missing parts Failure to obey can cause damage to the drive and connected equipment NOTICE Install fuses and an RCM RCD Failure to...

Page 8: ...uld cause a life or death situation loss of human life or a serious accident or physical injury About Registered Trademarks Powerlink is a registered trademark of Ethernet Powerlink Standardization Gr...

Page 9: ...re version see PRG on the nameplate of the AC drive or regenerative unit 3 Receiving Please perform the following tasks after receiving the Communication Option card Inspect the Communication Option c...

Page 10: ...cription Read the manual Obey the safety messages in the manual to prevent any kind of damage to humans or to the equipment Electrical Shock Hazard Correctly ground the drive before you turn on the EM...

Page 11: ...ink Option Components Powerlink Option SI EL3 A Communication cable connector RJ45 B Ground terminal installation hole C Model number D Installation hole E LED S E F LED MS G LED L A 2 H LED L A 1 I C...

Page 12: ...tor Specification LEDs L A OUT and L A IN Ethernet Link Activity 1 and 2 The Link Activity indicators show the status of the physical link and show activity on the link period LED Color Display Meanin...

Page 13: ...ash The device is in NMT_CS_PRE_OPERATIONAL_1 state Green Double flash The device is in NMT_CS_PRE_OPERATIONAL_2 state Green Triple flash The device is in NMT_CS_READY_TO_OPERATE state Green On The de...

Page 14: ...he Communication Option card is connected to the network using a RJ45 connector flickering on 50 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 200 ms 20...

Page 15: ...card 5 Mechanical Electrical Installation Safety Precautions DANGER Electrical Shock Hazard Do not examine connect or disconnect wiring on an energized drive Before servicing disconnect all power to...

Page 16: ...interference and unsatisfactory system performance NOTICE Do not change the drive circuitry Failure to obey can cause damage to the drive and will void warranty Yaskawa is not responsible for modifica...

Page 17: ...erator I LED labels J Front cover Figure 5 1 Installing the Option Card on a A1000 D1000 R1000 or U1000 5 Prepare the RJ45 network cable connectors For drives CIMR Ax2A0004 to 2A0040 and 4A0002 to 4A0...

Page 18: ...ctor to the option 7 Reinstall the front cover back onto the drive as it was before 8 Attach the LED label I as shown in Figure 5 1 9 Switch on the drive power supply Installing the Option on a V1000...

Page 19: ...ossible cable for ground connection 4 Re attach the bottom cover 5 Connect the Communication Option card to the drive Properly secure the tabs on the left and right side of the Communication Option ca...

Page 20: ...ar connector 8 Attach the cover to the front of the Communication Option card 9 Switch on the drive power supply Installing the Option on a GA800 GA700 or CR700 A Insertion for CN5 connector B Option...

Page 21: ...on the drive control board 1 Affix the LED label E in the appropriate position on the drive front cover D Figure 5 7 Affix the LED Label 2 Turn off the power Wait until the CHARGE LED turns off and th...

Page 22: ...e The option package ships with three screws and a ground wire for installation on other drive series Do not use the ground wire or the extra screw Figure 5 10 Insert the Option Card 6 Firmly connect...

Page 23: ...Keypad 10 Switch on the drive power supply Installing the Option on a GA500 If you want to install the option card on a GA500 AC drive you must use the Option Card Mounting Kit Model JOHB GA500 The i...

Page 24: ...A J Connector CN5 B Not for communication option installation K Connector CN5 C Not for communication option installation Figure 5 12 Q2A Components with Option Card The procedures for removing and r...

Page 25: ...urn off the power Wait until the CHARGE LED turns off and then remove the cover Refer to the drive manual for direction on removing the front cover 3 Move the keypad connector to the holder on the dri...

Page 26: ...d wire The option package ships with three screws and a ground wire for installation on other drive series Do not use the ground wire or the extra screw Figure 5 16 Insert the Option Card 6 Firmly con...

Page 27: ...manual that is shipped with that option Communication option cards can only be inserted into the CN5 A connector located on the drive control board XDD File For easy network implementation of drives...

Page 28: ...ction after Communications Error Determines drive response when a bUS error is detected during communications with the Communication Option 0 Ramp to Stop 1 Coast to Stop 2 Fast Stop 3 Alarm Only 3 1...

Page 29: ...If set to 3 then the drive will continue to operate when an EF0 fault is detected Take proper safety measures such as installing an emergency stop switch 4 This parameter might not appear in certain d...

Page 30: ...3221 SoftCharge Bypass Circuit Fault Uv3 04 2340 Out Short Circuit or IGBT Fault SC 05 2330 Ground Fault GF 06 2220 Overcurrent oC 07 3210 DC Bus Overvoltage ov 08 4280 Heatsink Overheat oH 09 4210 H...

Page 31: ...ion Fault CE 21 FF04 Option Communication Error bUS 22 FF05 Control Fault CF 25 8313 Zero Servo Fault SvE 26 5481 Option Card External Fault EF0 27 FF06 PID Feedback Loss FbL 28 FF07 Undertorque Detec...

Page 32: ...Detection 1 oL5 44 FF20 Mechanical Weakening Detection 2 UL5 45 FF21 Current Offset Fault CoF 46 FF22 PLC Detection Error 1 PE1 47 FF23 PLC Detection Error 2 PE2 48 FF24 DriveWorksEZ Fault dWFL 49 63...

Page 33: ...Power Supply Frequency Fault Fdv 68 FF3D Phase Order Detection Fault SrC 69 FF3E Power Supply Undervoltage Pre Alarm PAUv 6B FF3F AC Fuse Blowout FUA 70 FF40 Resonance Detection vrE 71 FF41 Control C...

Page 34: ...de Error CPF31 A0 FF5C ASIC Start up Error CPF32 A1 FF5D Watchdog Circuit Exception Circuit Fault CPF33 A2 FF5E ASIC Power Clock Error CPF34 A3 FF5F External A D Conversion Failure CPF35 A4 FF60 ASIC...

Page 35: ...rt CN5 A oFA17 118 FF78 Comm ID Error oFA30 131 FF79 Model Code Error oFA31 132 FF7A Checksum Error oFA32 133 FF7B Comm option timeout waiting for response oFA33 134 FF7C MEMOBUS Modbus communications...

Page 36: ...234 FF97 MEMOBUS Modbus communications timeout oFb34 235 FF98 Drive timeout waiting for response oFb35 236 FF99 CI Check Error oFb36 237 FF9A Drive timeout waiting for response oFb37 238 FF9B Control...

Page 37: ...at Option Port oFC52 353 FFB1 Option Card Error Occurred at Option Port oFC53 354 FFB2 Option Card Error Occurred at Option Port oFC54 355 FFB3 Option Card Error Occurred at Option Port oFC55 356 FFB4...

Page 38: ...drive did not receive a signal from the controller The communications cable wiring is incorrect Correct wiring errors There is a short circuit in the communications cable or the communications cable...

Page 39: ...rect connector Note DO A3 AO A3 PG B3 and PG X3 options can connect to connector CN5 B To connect only one PG option card use the CN5 C connector oFb02 Duplicate Options The same option cards or the s...

Page 40: ...r Indication Possible Solution Initial power up sequence not completed within 10 seconds Possible cause Drive is not processing the internal interface protocol Drive does not support this communicatio...

Page 41: ...ng is faulty there is a short circuit or something is not connected properly Correct any wiring errors EEPROM checksum error If these errors occur the object dictionary will be reset to its default va...