12
YASKAWA
SIEP C730600 0E YAI Modbus TCP/IP Technical Manual
Product Series
Procedures to Install and Wire Options on a Drive
Page
Z1000
Procedure B
GA500
-
GA700
Procedure C
GA800
Procedure C
HV600
Procedure D
*1
To install the option on GA500 drives, use the option mounting kit (JOHB-GA50) and manual.
*2
Before you install the option on a YASKAWA AC Drive GA500, make sure that the option software version is PRG: 0383 or later.
■
Procedure A
This section shows the procedure to install and wire the option on a 1000-series drive.
Prepare the Drive for the Option
Correctly wire the drive as specified by the manual packaged with the drive. Make sure that the drive functions
correctly. Refer to the drive manuals for more information.
A - Insertion point for CN5 connector
B - Option
C - Drive front cover
D - Keypad
E - LED label
F - Drive terminal cover
G - Removable tabs for wire routing
H - Included screws
I - Ground wire
J - Option modular connector CN1 port 1 (RJ45)
K - Option modular connector CN1 port 2 (RJ45)
L - Drive grounding terminal (FE)
M - Connector CN5-A
N - Connector CN5-B (Not available for
communication option installation.)
O - Connector CN5-C (Not available for
communication option installation.)
Figure 5.1 Drive Components with Option
Install the Option
Use this procedure to install the option.
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.
1.
Remove the keypad (B), front cover (A), and terminal cover (C).
Shut off power to the drive and wait for the time specified on the drive warning label at a minimum. Make
sure that the charge indicator LED is unlit, then remove the keypad and front cover. Refer to the drive
manuals for more information.
You can only install this option into the CN5-A connector on the drive control board.
NOTICE
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic
discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry.
F
H
M
N
O
L
K
I
B
C
D
A
G
J
E