5 Installation Procedure
YASKAWA ELECTRIC
SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
17
6. Connect the ground wire between the drive ground terminal and the EtherNet/IP Option ground. When wiring the
EtherNet/IP Option, pass the ground wire through the inside of the drive bottom cover, then pass the ground wire into
the through-hole for the ground wire at the front of the EtherNet/IP Option.
Figure 9
Figure 10 Ground Wire Connection
7. Connect the communication wire to the EtherNet/IP Option modular connector. Refer to Procedure on page
8. Attach the EtherNet/IP Option cover to the front of the EtherNet/IP Option.
Figure 10
Figure 11 Attach Cover
Communication Cable Wiring
Procedure
To connect the EtherNet/IP Option to a network, insert a RJ45 8-pin Straight Connector STP Cat 5e cable into the
modular connector port. Ensure the cable end is firmly connected.
Note:
Only use cable recommended for EtherNet/Industrial Protocol (EtherNet/IP™). Using a cable not specifically recommended may
cause the EtherNet/IP Option or drive to malfunction.
Note:
Replace the option cover after all wiring is completed.
Figure 11
Figure 12 Communication Cable Port
Drive ground
terminal
Through-hole
for ground wire
Ground wire
Pass the ground
wire through
the bottom cover
of the drive.
Tabs should line up