7 EtherNet/IP Option Drive Parameters
YASKAWA ELECTRIC
SIEP YEACOM 01A V1000 Option EtherNet/IP Technical Manual
23
Table 9 EtherNet/IP Option Monitors
F7-17
EtherNet/IP Speed Scaling Factor
Sets the scaling factor for the speed monitor in EtherNet/IP Class ID 2AH Object
0
F7-18
EtherNet/IP Current Scaling Factor
Sets the scaling factor for the output current monitor in EtherNet/IP Class ID 2AH
Object
0
F7-19
EtherNet/IP Torque Scaling Factor Sets the scaling factor for the torque monitor in EtherNet/IP Class ID 2AH Object
0
F7-20
EtherNet/IP Power Scaling Factor Sets the scaling factor for the power monitor in EtherNet/IP Class ID 2AH Object
0
F7-21
EtherNet/IP Voltage Scaling Factor Sets the scaling factor for the voltage monitor in EtherNet/IP Class ID 2AH Object
0
F7-22
EtherNet/IP Time Scaling
Sets the scaling factor for the time monitor in EtherNet/IP Class ID 2AH Object
0
F7-23 to
F7-32
Dynamic Output Assembly
Parameters
Parameters used in Output Assembly 116. Each parameter contains a MEMOBUS/
Modbus address. The value received for Output Assembly 116 will be written to this
corresponding MEMOBUS/Modbus address. A MEMOBUS/Modbus address value
of 0 means that the value received for Output Assembly 116 will not be written to
any MEMOBUS/Modbus register.
0
F7-33 to
F7-42
Dynamic Input Assembly
Parameters
Parameters used in Input Assembly 166. Each parameter contains a MEMOBUS/
Modbus address. The value sent for Input Assembly 166 will be read from this
corresponding MEMOBUS/Modbus address. A MEMOBUS/Modbus address value
of 0 means that the value sent for Input Assembly 166 is not defined by the user,
therefore the SI-EN3 default register value will be returned.
Torque Status Input (Vendor Specific YEA Assy) - 166 (0xA6) on page 42
for
definitions of the default MEMOBUS/Modbus registers.
0
<1> To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to “3“. To control drive frequency
reference via the master device, set b1-01 to “3”.
<2> If F6-01 is set to 3, then the drive will continue to operate when a bUS error or an EF0 fault is detected. Take proper safety measures, such as
installing an emergency stop switch.
<3> Software versions 1012 and later have F6-07 and F6-08 both set to 1.
Function
Monitor
Value Range
Description
Online IP Address
U6-80 to U6-83
0 to 255
IP Address; U6-80 is the most significant octet
Online Subnet
U6-84 to U6-87
0 to 255
Subnet; U6-84 is the most significant octet
Online Gateway
U6-88 to U6-91
0 to 255
Gateway; U6-88 is the most significant octet
Online Speed
U6-92
10, 100
Link Speed
Online Duplex
U6-93
0: Half, 1: Full
Duplex Setting
First Fault
U6-98
-
First Option Board Fault
Current Fault
U6-99
-
Current Option Board Fault
No.
Name
Description
Default