9 Option Drive Parameters
9
Option Drive Parameters
Before starting network communications, verify proper setting of drive parameters in
using the drive digital operator.
Table 10 Parameter Settings
No.
Name
Description
Default
b1-01
Frequency Reference
Selection
Selects the frequency reference input source.
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminal A1 or A2
2: MEMOBUS/Modbus communications
3: Option PCB
4: Pulse Input (Terminal RP)
1
(Set to 3 for
PROFINET)
b1-02
Run Command Selection
Selects the run command input source.
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S1 to S7
2: MEMOBUS/Modbus communications
3: Option PCB
1
(Set to 3 for
PROFINET)
F6-01
Operation Selection after
Communications Error
Determines drive response when a bUS error is
detected during communications with the option.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
4: Alarm (d1-04)
5: Alarm Ramp to Stop
1
F6-02
External Fault Detection
Conditions (EF0)
Sets the condition for external fault detection (EF0).
0: Always detected
1: Detected only during operation
0
F6-03
Stopping Method for External
Fault from Communication
Option Board
Determines drive response for external fault input
(EF0) detection during communication.
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only
1
F6-07
NetRef/ComRef Selection
Function
0: Multi-step speed reference disabled
1: Multi-step speed reference allowed
1
F6-08
Reset Communication Related
Parameters
Determines if communication-related parameters F6-
and F7-
are set back to original default
values when the drive is initialized using parameter
A1-03.
0: Do not reset F6-
and F7-
parameters
1: Reset F6-
and F7-
parameters
Note:
Setting this parameter does not affect
communication-related parameters.
0