Troubleshooting
Drive-Side Error Codes
Drive-side error codes appear on the drive digital operator. Causes of the errors and corrective actions are listed in
. For additional error codes that may appear on the drive digital operator, refer to the drive Technical Manual
available at
http://www.yaskawa.com.
Faults
Both bUS (Option Communication Error) and EF0 (External Fault Input from the option) can appear as an alarm or as a
fault. When a fault occurs, the digital operator ALM LED remains lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to help remedy the fault:
• Is the option properly installed?
• Is the communication line properly connected to the option? Is it loose?
• Is the controller program working? Has the controller/PLC CPU stopped?
• Did a momentary power loss interrupt communications?
Table 29 Fault Display and Possible Solutions
LED Operator Display
Fault Name
bUS
Option Communication Error.
After establishing initial communication, the connection was lost.
Only detected when the run command or frequency reference is assigned to the option (b1-01 =
3 or b1-02 = 3).
Cause
Possible Solution
Master controller (PLC) has stopped
communicating.
• Check that power is supplied to the PLC
• Check that PLC is not in program mode
Communication cable is not connected properly.
• Check for faulty wiring
• Correct any wiring problems
A data error occurred due to noise.
• Check the various options available to minimize the effects of noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to the
contactor coil
• Make sure the cable used meets the option requirements
• Make sure the option ground wire is connected between option FE terminal and the drive
ground terminal connected to earth ground
Option is damaged.
If there are no problems with the wiring and the error continues to occur, replace the option.
LED Operator Display
Fault Name
EF0
External Fault Input from the option.
The alarm function for an external device is triggered.
Cause
Corrective Action
An external fault is being sent from the upper
controller (PLC).
• Remove the cause of the external fault
• Reset the external fault input from the PLC device
Problem with the PLC program.
Check the program used by the PLC and make the appropriate corrections.
LED Operator Display
Fault Name
oFA00
Option Fault.
Option is not properly connected.
Cause
Possible Solution
Non-compatible option connected to the drive.
Connect an option that is compatible with the drive.