Connector
Table 4.1 Communication Connector
MECHATROLINK-III Connector
Pin No.
Signal Name
I/O
Function
1
TXD_P
I/O
Send data (+): OUT
2
TXD_N
I/O
Send data (-): OUT
3
RXD_P
I/O
Receive data (+): IN
4
(NC)
-
-
5
(NC)
-
-
6
RXD_N
I/O
Receive data (-): IN
7
(NC)
-
-
8
(NC)
-
-
Shell
SLD
-
Shield
◆
MECHATROLINK-II Option LED Display
Option has four LEDs that identify the option card or communication status.
■
Defining Option LED States
A - 1000-Series Label
B - GA500, GA700, GA800, CR700,
and CH700 Label
Figure 4.2 Option LED Labels
Table 4.2 MECHATROLINK-II Operation LED Status
Name
State
Operating Status
Description
R/E
Lit in green
Power supply on
•
SI-ET3 has been successfully powered up
•
An internal, self-diagnostic check completed in the SI-ET3
Lit in red
Error
•
Error/alarm occurred
•
Command error occurred (parameter error, phase error, combination error)
Flashing in red
SI-ET3 error
Error found during the SI-ET3 self-diagnostic check
Unlit
Power supply off
•
The drive has no power
•
SI-ET3 is not properly connected to the drive, or SI-ET3 has no power
•
An internal, self-diagnostic error occurred in the SI-ET3
CON
Lit in green
Connection established
Established connection
Unlit
Connection unestablished
Connection with master device is not established
LK1
Lit in green
Connector CN1 connected
Connector CN1 is connected to other stations
Unlit
Connector CN1 disconnected
Connector CN1 is not connected to other stations (cable not connected, cable
disconnected, other stations not powered up)
LK2
Lit in green
Connector CN2 connected
Connector CN2 is connected to other stations
Unlit
Connector CN2 disconnected
Connector CN2 is not connected to other stations (cable not connected, cable
disconnected, other stations not powered up)
5
Installation Procedure
◆
Section Safety
DANGER
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an energized drive. Before
servicing, disconnect all power to the equipment and wait for the time specified on the warning label at a minimum. The internal
capacitor stays charged after the drive is de-energized. The charge indicator LED extinguishes when the DC bus voltage
decreases below 50 Vdc. When all indicators are OFF, measure for dangerous voltages to make sure that the drive is safe. If
you do work on the drive when it is energized, it will cause serious injury or death from electrical shock.