6 Utility Functions (Fn
)
6-12
6.6
Initializing Parameter Settings (Fn005)
This function is used when returning to the factory settings after changing parameter settings.
Note: Any value adjusted with Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.
(1) Preparation
The following conditions must be met to initialize the parameter values.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servomotor power must be OFF.
(2) Operating Procedure
Use the following procedure.
• Be sure to initialize the parameter settings while the servomotor power is OFF
.
• After initialization, always turn the control power supply OFF and ON again to validate
the settings.
Step
Display after Operation
Keys
Operation
1
Press the
Key to view the main menu for the
utility function.
Use the
or
Key to move through the list and
select Fn005.
2
Press the
Key. The display changes to the Fn005
execution display.
3
Press the
Key to initialize parameters.
During initialization, "Parameter Init" is flashing in
the display.
After the initialization is completed, "Parameter Init"
stops flashing and the status display changes as fol-
lows: "BB" to "DONE" to "BB."
Note: Press the
Key not to initialize parameters.
The display returns to the main menu of the
utility function.
4
When you finish initializing the parameter settings, turn the control power supply OFF and ON again.
B B
−
F U N C T I O N
−
F n 0 0 4 : P r o g r a m J O G
F n 0 0 5 : P r m I n i t
F n 0 0 6 : A l m H i s t C l r
F n 0 0 8 : M t u r n C l r
B B
P a r a m e t e r l n i t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]
B B
P a r a m e t e r l n i t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]