With this CPU exclusively Siemens S7 connection may be configured with Siemens
NetPro.
n
For data transfer with Siemens S7 connections the FB/SFB Yaskawa handling blocks
are necessary; the deployment is described in the manual "Operation list" of your
CPU.
n
At Siemens S7 connections the communication connections are specified by a con-
nection ID for each communication partner.
n
A connection is specified by the local and partner connection end point.
n
At Siemens S7 connections the TSAPs must be congruent crosswise. The following
parameters define a connection end point:
The following parameters define a connection end point:
Station A
Station B
remote TSAP
à
Siemens
S7 connection
à
local TSAP
local TSAP
ß
ß
remote TSAP
ID A
ID B
Combination options with deployment of the FB/SFB Yaskawa handling blocks
Connection partner
Connection establishing
Connection
specified in NetPro
(in the current project)
active/passive
specified
unspecified in NetPro
(in the current project)
active
specified
passive
unspecified
unspecified in NetPro
(in the unknown project)
active/passive
specified (connection name in an other
project)
Connection types
Siemens S7 connection
System 300S
+
Deployment Ethernet communication - productive
Configure Siemens S7 connections
HB140 | CPU | 315-4PN23 | en | 18-02