9.7 Parameters - PROFINET IO controller
9.7.1 Precondition
To parametrize the PROFINET IO controller of the CPU, the following conditions must be
fulfilled:
n
The PROFINET IO controller is online reachable, this means an initialization was
established.
n
The hardware configuration described before was established and the PROFINET IO
controller is networked.
Open the properties dialog of the PROFINET IO controller by a double-click at PN-
IO.
The PROFINET interface of the PROFINET IO controller is parametrized with
PN-IO
, the
port with Port 1. In the following these parameters for PN-IO and Port 1 are described.
9.7.2 PN-IO
Designation of the IO controller. The IO controller from VIPA always has the
short
description
"PN-IO".
The device name on the Ethernet subnet must be unique. For an integrated PROFINET
interface the device name is derived from the short description.
Here the purpose may be entered for which the IO controller is being used.
With properties you can enter the IP address, subnet mask and gateway for the
PROFINET interface and select the subnet to be connected.
The CPU reports errors of the IO controller via the
interface address
, as soon as e.g. an
error during synchronization of the IO controller occurs. With the
PROFINET IO system
address
the CPU reports e.g. failure/return of the PROFINET IO system. This address is
also used to identify the IO system to which the device belongs, if an IO device fails.
With the operation field "OB82 / I/O fault task..." you can cause the CPU to call the OB 82
at an error event of the PROFINET interface. An entry to the diagnostics buffer is always
done.
The other parameters in this tab are not relevant for the use of the VIPA PROFINET CPU.
Proceeding
General
Short description
Device name
Comment
Properties
Addresses
PROFINET
System 300S
+
Deployment Ethernet communication - PROFINET
Parameters - PROFINET IO controller > PN-IO
HB140 | CPU | 315-4PN23 | en | 18-02
128