You get valid IP address parameters from your system administrator. The assignment of
the IP address data happens online in the Siemens TIA Portal with the following pro-
ceeding:
1.
Start the Siemens TIA Portal.
2.
Switch to the
‘Project view’
.
3.
Click in the
‘Project tree’
at
‘Online access’
and choose here by a double-click your
network card, which is connected to the PROFINET interface X8.
4.
To get the stations and their MAC address, use the
‘Accessible device’
. The Mac
address can be found at the 2. label beneath the front flap of the CPU.
5.
Choose from the list the module with the known MAC address (PROFINET CP
[MAC address]) and open with "Online & Diagnostics" the diagnostics dialog in the
Project area.
6.
Navigate to
Functions > Assign IP address
. Type in the IP configuration like IP
address, subnet mask and gateway.
7.
Confirm with [Assign IP configuration].
ð
Directly after the assignment the PROFINET interface is online reachable using
the set IP address data. The value remains as long as it is reassigned, it is
overwritten by a hardware configuration or a factory reset is executed.
Due to the system you may get a message that the IP address could not
be assigned. This message can be ignored.
Assign IP address param-
eters
System 300S
+
Configuration with TIA Portal
TIA Portal - Hardware configuration - PG/OP via PROFINET
HB140 | CPU | 315-4PN23 | en | 18-02
147